Parameters 141
11.03
Stop mode
Selects the motor stop function.
Coast
Stop by cutting of the motor power supply. The motor coasts
to a stop.
WARNING!
If the mechanical brake is used, ensure it
is safe to stop the drive by coasting.
1
Ramp
Stop along ramp. See parameter group
2
11.04
Dc hold speed
Defines the DC hold speed. See parameter
.
0.0 … 1000.0 rpm
DC hold speed.
10 = 1 rpm
11.05
Dc hold curr ref
Defines the DC hold current in percent of the motor nominal
current. See parameter
0 … 100%
DC hold current.
1 = 1%
11.06
Dc hold
Enables the DC hold function. The function makes it possible
to lock the rotor at zero speed.
When both the reference and the speed drop below the
value of parameter
, the drive will stop
generating sinusoidal current and start to inject DC into the
motor. The current is set by parameter
. When the reference speed exceeds parameter
, normal drive operation continues.
Notes:
• The DC hold function has no effect if the start signal is
switched off.
• The DC hold function can only be activated in speed
control mode.
• The DC hold function cannot be activated if parameter
is set to
• Injecting DC current into the motor causes the motor to
heat up. In applications where long DC hold times are
required, externally ventilated motors should be used. If
the DC hold period is long, the DC hold cannot prevent
the motor shaft from rotating if a constant load is applied
to the motor.
Disabled
The DC hold function is disabled.
0
Enabled
The DC hold function is enabled.
1
12
12 Operating mode
Selection of external control location and EXT2 operating
mode.
12.01
Ext1/Ext2 sel
Selects the external control location (EXT1 or EXT2), or the
source of a selection signal (0 = EXT1; 1 = EXT2).
Ext1
EXT1 is active.
0
No.
Name/Value
Description
FbEq
Reference
Motor speed
DC hold
t
t
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...