Parameters 97
Start inhibit status word. This word specifies the
source of the inhibiting signal that is preventing
the drive from starting.
The conditions marked with an asterisk (*) only
require that the start command is cycled. In all
other instances, the inhibiting condition must be
removed first.
See also parameter
, bit 1.
This parameter is read-only.
0b0000
0b0000...0b1111 Start inhibit status word.
1 = 1
No.
Name/Value
Description
Def/
FbEq16
Bit
Name
Description
0
Not ready run
1 = DC voltage is missing or drive has not been
parametrized correctly. Check the parameters in
groups 95 and 99.
1
Ctrl location
changed
* 1 = Control location has changed
2
SSW inhibit
1 = Control program is keeping itself in inhibited
state
3
Fault reset
* 1 = A fault has been reset
4
Reserved
5
Lost run enable
1 = Run enable signal missing
6
Reserved
7
STO
1 = Safe torque off function active
8
Current calibration
ended
* 1 = Current calibration routine has finished
9
ID run ended
* 1 = Motor identification run has finished
10
Reserved
11
Em Off1
1 = Emergency stop signal (mode off1)
12
Em Off2
1 = Emergency stop signal (mode off2)
13
Em Off3
1 = Emergency stop signal (mode off3)
14
Auto reset inhibit 1 = The autoreset function is inhibiting operation
15
Reserved
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...