Program features 57
Settings
•
Menu
-
Primary settings
-
Motor
-
Control mode
(page
(page
Speed control performance
The figure below shows the typical speed control performance.
Switching frequency
The drive has two switching frequency settings: reference switching frequency
and minimum switching frequency. The drive tries to keep the highest allowed
switching frequency (= reference switching frequency) if thermally possible, and
then adjusts dynamically between the reference and minimum switching
frequencies depending on the drive temperature. When the drive reaches the
minimum switching frequency (= lowest allowed switching frequency), it starts
to limit output current if the heating up continues.
For derating, see chapter
Technical data
, section
Switching frequency derating
in
the
Hardware manual
of the drive.
Example 1:
If you need to fix the switching frequency to a certain value with
some external filters as required, set both the reference and the minimum
switching frequency to this value and the drive will retain this switching
frequency.
Example 2:
If the reference switching frequency is set to 12 kHz and the
minimum switching frequency is set to the smallest available value, the drive
maintains the highest possible switching frequency to reduce motor noise and
only when the drive heats up it will decrease the switching frequency. This is
100
t
(s)
T
T
N
(%)
T
load
n
act
-n
ref
n
N
Area < 10% s
T
N
= rated motor torque
n
N
= rated motor speed
n
act
= actual speed
n
ref
= speed reference
Speed control
Performance
Static accuracy
20% of motor nominal
slip
Dynamic accuracy < 10% s with 100%
torque step (with
default speed controller
tuning)
Tuned speed
controller
< 2% s with 100%
torque step
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...