308 Fault tracing
A2BA IGBT overload
Excessive IGBT junction
to case temperature.
This warning protects
the IGBT(s) and can be
activated by a short
circuit in the motor cable.
Check motor cable.
Check ambient conditions.
Check air flow and fan
operation.
Check heatsink fins for dust
pick-up.
Check motor power against
drive power.
A3A1 DC link
overvoltage
Intermediate circuit DC
voltage too high (when
the drive is stopped).
Check the supply voltage setting
(parameter
Note that the wrong setting of
the parameter may cause the
motor to rush uncontrollably.
Check the supply voltage.
If the problem persists, contact
your local ABB representative.
A3A2 DC link
undervoltage
Intermediate circuit DC
voltage too low (when
the drive is stopped).
A3AA DC not charged
The voltage of the
intermediate DC circuit
has not yet risen to
operating level.
A490 Incorrect
temperature
sensor setup
Sensor type mismatch
Check the settings of
temperature source parameters
against
91.21
and
91.25.
A491 External
temperature 1
(Editable message
text)
Measured temperature 1
has exceeded warning
limit.
Check the value of parameter
.
Check the cooling of the motor
(or other equipment whose
temperature is being measured).
Check the value of
.
A492 External
temperature 2
(Editable message
text)
Measured temperature 2
has exceeded warning
limit.
Check the value of parameter
.
Check the cooling of the motor
(or other equipment whose
temperature is being measured).
Check the value of
.
A4A0 Control board
temperature.
Control board
temperature is excessive.
1 – Sensor fault.
Check the sensor and change
the control board.
Code
(hex)
Warning / Aux.
code
(
aux code visible
only on assistant
control panel and drive
composer)
Cause
What to do
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...