230 Parameters
Selects the interlock source for pump start and
stop. When the interlock is disabled, pump
cannot be started in any operating modes and
tank level sensor operation cannot function.
Disable
0 = Pump start interlock is disabled.
0
Enable
1 = Pump start interlock is enabled.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
Source selection (see
on
page
-
Defines the minimum DC voltage for drive to
start running the pump motor. The pump motor
stops running if the voltage goes below this
value.
Note:
If you change this value while the inverter is
running, the changed value is effective only
during the
next start
225
225...800 V
DC voltage.
1 = 1
Defines the minimum DC voltage below which
the
drive turns off all the controls.
Note:
The drive stops operating below this
voltage.
225
225...800 V
DC voltage.
1 = 1
Defines the maximum DC voltage. At any value
above this voltage, the drive trips due to
fault.
800
225...800 V
DC voltage.
1 = 1
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...