158 Parameters
Source selection (see
).
-
Selects the source for tank high level sensor enable signal.
0 = Not selected.
1 = Selected.
See parameter
.
Defines the pump start time. This feature is used with timed
function.
Note:
Timed function must be enabled to use this feature.
See parameter
00:00:00
00:00:00...
23:59:59
Pump start time.
1 = 1
Defines the pump stop time. This feature is used with timed
function.
Note:
Timed function must be enabled to use this feature.
See parameter
00:00:00
00:00:00...
23:59:59
Pump stop time.
1 = 1
Selects the source for MPPT reference enable signal.
0 = Disabled
1 = Enabled
Disable
MPPT reference is not activated.
0
Enable
MPPT reference is activated.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
Source selection (see
).
-
Defines the minimum DC voltage to start the drive.
Note:
If you change this value while the inverter is
running, the changed value is effective only during the
next start
225
225...800 V
DC voltage.
1 = 1
Defines the minimum DC voltage below which the
drive cannot operate.
Note:
The drive stops operating below this voltage.
225
225...800 V
DC voltage.
1 = 1
Defines the maximum DC voltage. At any value above
this voltage, the drive trips due to
fault.
800
225...800 V
DC voltage.
1 = 1
Defines the minimum motor speed. At any value below
this speed, the drive stops functioning and auto
restarts after the time defined in
. This
setting avoids unnecessary operation of pump at low speed.
200
0...3000 rpm
Speed.
1 = 1
No.
Name/Value
Description
Def/FbEq16
ACQ80 FW.book Page 158 Thursday, February 14, 2019 11:33 AM
Summary of Contents for ACQ80-04 Series
Page 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Page 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Page 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Page 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Page 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Page 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Page 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...