Parameters 259
Defines the start point for the first auxiliary motor. As the
motor speed or frequency exceeds the limit defined by this
parameter, a new auxiliary motor is started.
To avoid nuisance starts of the second auxiliary motor, the
speed of the variable speed motor should be higher than the
start speed for the duration defined by parameter
. If the speed decreases below the start speed, the
auxiliary motor is not started.
To maintain the process conditions during the start of the
second auxiliary motor, a speed hold on time can be defined
with parameter
. Certain pump
types do not produce significant flow with low frequencies.
The speed hold on time can be used to compensate the time
needed to accelerate the second auxiliary motor to a speed
where it produces flow. The start of the second auxiliary
motor is not aborted if the speed of the first auxiliary motor
decreases
Vector:
1300 rpm;
Scalar 48 Hz;
58 Hz
(
b0);
20.00; 30.00
0.00…32767.00
[rpm/Hz] [m]
Speed/frequency.
1 = 1 unit
Defines the start point for the second auxiliary motor. See
parameter
Vector:
1300 rpm;
Scalar 48 Hz;
58 Hz
(
b0);
25.00
Defines the start point for the third auxiliary motor. See
parameter
Vector:
1300 rpm;
Scalar 48 Hz;
58 Hz
(
b0);
30.00; 20.00
No.
Name/Value
Description
Def/FbEq16
Increasing
flow
Speed
Time
Stop
Start
Decreasing
flow
A
ux
. pump
1
S
top/S
tar
t
ON
ON
OFF
OFF
Min. speed
Max. speed
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...