254 Parameters
Parameter selector for Modbus register address 400007.
For the selections, see parameter
.
…
…
…
…
Parameter selector for Modbus register address 400014.
For the selections, see parameter
.
71
Configuration of external PID.
See the control chain diagrams on pages
and
.
See parameter
-
See parameter
-
See parameter
.
-
See parameter
-
Displays status information on process external PID control.
This parameter is read-only.
-
0000h…FFFFh
Process PID control status word.
1 = 1
See parameter
See parameter
See parameter
.
0.000 s
Defines, together with parameter
general scaling factor for the external PID control chain. The
scaling can be utilized when, for example, the process
setpoint is input in Hz, and the output of the PID controller is
used as an rpm value in speed control. In this case, this
parameter might be set to 50, and parameter
nominal motor speed at 50 Hz.
In effect, the output of the PID controller [
] when
deviation (setpoint - feedback) = [
] = 1.
Note:
The scaling is based on the ratio between
and
. For example, the values 50 and 1500 would produce
the same scaling as 1 and 3.
100.00
-200000.00…
200000.0
Process setpoint base.
1 = 1
See parameter
100.00
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Value
0
PID active
1 = Process PID control active.
1
Reserved
2
Output frozen
1 = Process PID controller output frozen. Bit is set if parameter
is TRUE, or the deadband function is
active (bit 9 is set).
3…6
Reserved
7
Output limit high
1 = PID output is being limited by par.
.
8
Output limit low
1 = PID output is being limited by par.
9
Deadband active
1 = Deadband is active.
10…11 Reserved
12
Internal setpoint
active
1 = Internal setpoint active (see par.
…
13…15 Reserved
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...