242 Parameters
Selects the type and scaling of reference 2 received from
fieldbus adapter A. The scaling of the reference is defined by
parameters
, depending on which reference
type is selected by this parameter.
Speed or frequency Type and scaling is chosen automatically according to the
currently active operation mode as follows:
Please select Speed (selection 4) or Frequency (selection 5)
manually.
0
Transparent
No scaling is applied.
1
General
Generic reference without a specific unit.
2
Reserved
3
Speed
The scaling is defined by parameter
.
4
Frequency
The scaling is defined by parameter
. 5
Selects the source of the Status word to be sent to the
fieldbus network through fieldbus adapter A.
Auto
Source of the Status word is chosen automatically.
0
Transparent mode
The source selected by parameter
is transmitted as the Status word to the
fieldbus network through fieldbus adapter A.
1
Selects the type and scaling of actual value 1 transmitted to
the fieldbus network through fieldbus adapter A. The scaling
of the value is defined by parameters
…
,
depending on which actual value type is selected by this
parameter.
Speed or frequency Type and scaling is chosen automatically according to the
currently active operation mode as follows:
0
Transparent
No scaling is applied.
1
General
Generic reference without a specific unit.
2
Reserved
3
Speed
The scaling is defined by parameter
.
4
Frequency
The scaling is defined by parameter
. 5
No.
Name/Value
Description
Def/FbEq16
Operation mode
(see par.
Reference 2 type
Speed control
Frequency control
Operation mode
(see par.
)
Actual value 1 type
Speed control
Frequency control
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...