Technical data
Cooling
Air flow, 208…240 V drives
The following table lists heat loss and air flow data for 208…240 V drives.
Air flow, 380…480 V drives
The following table lists heat loss and air flow data for 380…480 V drives.
Cooling specifications
Method
Internal fan, flow direction from bottom to top.
Requirement
Free space above and below the ACQ550 drive: 200 mm (8 in).
Free space is not required on the drive’s sides – ACQ550 drives can be mounted
side-by-side.
Drive
Heat loss
Air flow
ACQ550-x1-
Frame size
W
BTU/hr
m
3
/h
ft
3
/min
-04A6-2
R1
55
189
44
26
-06A6-2
R1
73
249
44
26
-07A5-2
R1
81
276
44
26
-012A-2
R1
116
404
44
26
-017A-2
R1
161
551
44
26
-024A-2
R2
227
776
88
52
-031A-2
R2
285
973
88
52
-046A-2
R3
420
1434
134
79
-059A-2
R3
536
1829
134
79
-075A-2
R4
671
2290
280
165
-088A-2
R4
786
2685
280
165
-114A-2
R4
1014
3463
280
165
-143A-2
R6
1268
4431
404
238
-178A-2
R6
1575
5379
404
238
-221A-2
R6
1952
6666
404
238
-248A-2
R6
2189
7474
404
238
00467918.xls C
Drive
Heat loss
Air flow
ACQ550-x1-
Frame size
W
BTU/hr
m
3
/h
ft
3
/min
-03A3-4
R1
40
137
44
26
-04A1-4
R1
52
178
44
26
-06A9-4
R1
97
331
44
26
-08A8-4
R1
127
434
44
26
-012A-4
R1
172
587
44
26
-015A-4
R2
232
792
88
52
-023A-4
R2
337
1151
88
52
-031A-4
R3
457
1561
134
79
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...