ACQ550-U1 User’s Manual
197
Embedded fieldbus
Modbus protocol technical data
Overview
The Modbus® protocol was introduced by Modicon, Inc. for use in control
environments featuring Modicon programmable controllers. Due to its ease of use
and implementation, this common PLC language was quickly adopted as a de-facto
standard for integration of a wide variety of master controllers and slave devices.
Modbus is a serial, asynchronous protocol. Transactions are half-duplex, featuring a
single Master controlling one or more Slaves. While RS232 can be used for point-to-
point communication between a single Master and a single Slave, a more common
implementation features a multi-drop RS485 network with a single Master controlling
multiple Slaves. The ACQ550 features RS485 for its Modbus physical interface.
RTU
The Modbus specification defines two distinct transmission modes: ASCII and RTU.
The ACQ550 supports RTU only.
Feature summary
The following Modbus function codes are supported by the ACQ550.
Function
Code (Hex)
Description
Read Coil Status
0x01
Read discrete output status. For the ACQ550, the individual bits
of the control word are mapped to Coils 1…16. Relay outputs are
mapped sequentially beginning with Coil 33 (e.g. RO1=Coil 33).
Read Discrete Input
Status
0x02
Read discrete inputs status. For the ACQ550, the individual bits
of the status word are mapped to Inputs 1…16 or 1…32,
depending on the active profile. Terminal inputs are mapped
sequentially beginning with Input 33 (e.g. DI1=Input 33).
Read Multiple
Holding Registers
0x03
Read multiple holding registers. For the ACQ550, the entire
parameter set is mapped as holding registers, as well as
command, status and reference values.
Read Multiple Input
Registers
0x04
Read multiple input registers. For the ACQ550, the 2 analog
input channels are mapped as input registers 1 & 2.
Force Single Coil
0x05
Write a single discrete output. For the ACQ550, the individual bits
of the control word are mapped to Coils 1…16. Relay outputs are
mapped sequentially beginning with Coil 33 (e.g. RO1=Coil 33).
Write Single
Holding Register
0x06
Write single holding register. For the ACQ550, the entire
parameter set is mapped as holding registers, as well as
command, status and reference values.
Diagnostics
0x08
Perform Modbus diagnostics. Subcodes for Query (0x00),
Restart (0x01) & Listen Only (0x04) are supported.
Force Multiple Coils
0x0F
Write multiple discrete outputs. For the ACQ550, the individual
bits of the control word are mapped to Coils 1…16. Relay outputs
are mapped sequentially beginning with Coil 33 (e.g. RO1=Coil
33).
Write Multiple
Holding Registers
0x10
Write multiple holding registers. For the ACQ550, the entire
parameter set is mapped as holding registers, as well as
command, status and reference values.
Read/Write Multiple
Holding Registers
0x17
This function combines functions 0x03 and 0x10 into a single
command.
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...