170
ACQ550-U1 User’s Manual
8120
INTERLOCKS
Defines operation of the Interlock function. When the Interlock function is enabled:
• An interlock is active when its command signal is absent.
• An interlock is inactive when its command signal is present.
• The ACQ550 will not start if a start command occurs when the speed regulated motor’s interlock is active – the
control panel displays an alarm (2015,
PFC
I
LOCK
).
Wire each Interlock circuit as follows:
• Wire a contact of the motor’s On/Off switch to the Interlock circuit – the drive’s PFC logic can then recognize that
the motor is switched off and start the next available motor.
• Wire a contact of the motor thermal relay (or other protective device in the motor circuit) to the Interlock input – the
drive’s PFC logic can then recognize that a motor fault is activated and stop the motor.
0 =
NOT
SEL
– Disables the Interlock function. All digital inputs are available for other purposes.
• Requires 8118
AUTOCHNG
INTERV
= 0.0 (The Autochange function must be disabled if Interlock function is
disabled.)
1 =
DI
1 – Enables the Interlock function and assigns a digital input (starting with
DI
1) to the interlock signal for each
PFC relay. These assignments are defined in the following table and depend on:
• the number of PFC relays [number of parameters 1401…1403 and 1410…1412 with value = 31 (
PFC
)]
• the Autochange function status (disabled if 8118
AUTOCHNG
INTERV
= 0.0, and otherwise enabled).
Code Description
No. PFC
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI
1: Speed Reg Motor
DI
2…
DI
6: Free
Not allowed
1
DI
1: Speed Reg Motor
DI
2: First PFC Relay
DI
3…
DI
6: Free
DI
1: First PFC Relay
DI
2…
DI
6: Free
2
DI
1: Speed Reg Motor
DI
2: First PFC Relay
DI
3: Second PFC Relay
DI
4…
DI
6: Free
DI
1: First PFC Relay
DI
2: Second PFC Relay
DI
3…
DI
6: Free
3
DI
1: Speed Reg Motor
DI
2: First PFC Relay
DI
3: Second PFC Relay
DI
4: Third PFC Relay
DI
5…
DI
6: Free
DI
1: First PFC Relay
DI
2: Second PFC Relay
DI
3: Third PFC Relay
DI
4…
DI
6: Free
4
DI
1: Speed Reg Motor
DI
2: First PFC Relay
DI
3: Second PFC Relay
DI
4: Third PFC Relay
DI
5: Fourth PFC Relay
DI
6: Free
DI
1: First PFC Relay
DI
2: Second PFC Relay
DI
3: Third PFC Relay
DI
4: Fourth PFC Relay
DI
5…
DI
6: Free
5
DI
1: Speed Reg Motor
DI
2: First PFC Relay
DI
3: Second PFC Relay
DI
4: Third PFC Relay
DI
5: Fourth PFC Relay
DI
6: Fifth PFC Relay
DI
1: First PFC Relay
DI
2: Second PFC Relay
DI
3: Third PFC Relay
DI
4: Fourth PFC Relay
DI
5: Fifth PFC Relay
DI
6: Free
6
Not allowed
DI
1: First PFC Relay
DI
2: Second PFC Relay
DI
3: Third PFC Relay
DI
4: Fourth PFC Relay
DI
5: Fifth PFC Relay
DI
6: Sixth PFC Relay
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...