Action
Test the operation of the STO function when the motor is stopped.
•
Give a stop command for the drive (if running) and wait until the motor shaft is
at a standstill.
Make sure that the drive operates as follows:
•
Open the STO circuit. The drive generates an indication if one is defined for the
'stopped' state in parameter 31.22 (see the firmware manual).
•
Give a start command to verify that the STO function blocks the drive's operation.
The motor should not start.
•
Close the STO circuit.
•
Reset any active faults. Restart the drive and check that the motor runs normally.
Test the operation of the STO function when the motor is running.
•
Start the drive and make sure the motor is running.
•
Open the STO circuit. The motor should stop. The drive generates an indication
if one is defined for the 'running' state in parameter 31.22 (see the firmware
manual).
•
Reset any active faults and try to start the drive.
•
Make sure that the motor stays at a standstill and the drive operates as described
above in testing the operation when the motor is stopped.
•
Close the STO circuit.
•
Reset any active faults. Restart the drive and check that the motor runs normally.
Test the operation of the failure detection of the drive. The motor can be stopped
or running.
•
Open the 1st input channel of the STO circuit. If the motor was running, it should
coast to a stop. The drive generates an FA81 fault indication (see the firmware
manual).
•
Give a start command to verify that the STO function blocks the drive's operation.
The motor should not start.
•
Close the STO circuit.
•
Reset any active faults. Restart the drive and check that the motor runs normally.
•
Open the 2nd input channel of the STO circuit. If the motor was running, it should
coast to a stop. The drive generates an FA82 fault indication (see the firmware
manual).
•
Give a start command to verify that the STO function blocks the drive's operation.
The motor should not start.
•
Close the STO circuit.
•
Reset any active faults. Restart the drive and check that the motor runs normally.
Document and sign the validation test report which verifies that the safety function
is safe and accepted for operation.
The Safe torque off function 231
Summary of Contents for ACH580-31
Page 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 30: ...30 ...
Page 39: ...Operation principle 39 ...
Page 56: ...56 ...
Page 90: ...90 ...
Page 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Page 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Page 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Page 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Page 131: ...R6 Electrical installation North America NEC 131 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 166: ... Fan arrow must point up 166 Maintenance ...
Page 212: ...212 ...
Page 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Page 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Page 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Page 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Page 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Page 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Page 220: ...220 ...
Page 242: ...242 ...
Page 250: ...250 ...
Page 254: ...254 ...
Page 262: ...262 ...
Page 268: ...268 ...
Page 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Page 276: ...276 ...
Page 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...