Guidelines for installing the drive to a TT system
You can install the drive to a TT system under these conditions:
1. There is a residual current device in the supply system
2. The internal EMC filter is disconnected. If the EMC filter is not disconnected, its
leakage current will cause the residual current device to trip.
Note:
•
ABB does not guarantee the EMC category, because the internal EMC filter is
disconnected.
•
ABB does not guarantee the functioning of the ground leakage detector built inside
the drive.
•
In large systems the residual current device can trip without a real reason.
■
Identifying the earthing system of the electrical power network
WARNING!
Only a qualified electrical professional may do the work instructed in this section.
Depending on the installation site, the work may even be categorized as live
working. Continue only if you are an electrical professional certified for the work.
Obey the local regulations. If you ignore them, injury or death can occur.
To identify the earthing system, examine the supply transformer connection. See the
applicable electrical diagrams of the building. If that is not possible, measure these
voltages at the distribution board, and use the table to define the earthing system type.
1. input voltage line to line (U
L-L
)
2. input voltage line 1 to ground (U
L1-G
)
3. input voltage line 2 to ground (U
L2-G
)
4. input voltage line 3 to ground (U
L3-G
).
Electrical installation – North America 93
Summary of Contents for ACH480
Page 1: ... ABB DRIVES FOR HVAC ACH480 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 14: ...14 ...
Page 22: ...22 ...
Page 28: ...28 ...
Page 38: ...38 ...
Page 44: ...44 ...
Page 60: ...60 ...
Page 86: ...86 ...
Page 110: ...110 ...
Page 114: ...114 ...
Page 122: ...122 ...
Page 156: ...Frame R1 Frame R1 front side IP20 UL open type 156 Dimension drawings ...
Page 157: ... Frame R1 bottom rear IP20 UL open type Dimension drawings 157 ...
Page 158: ... Frame R1 front side UL Type 1 kit installed 158 Dimension drawings ...
Page 159: ... Frame R1 bottom rear UL Type 1 kit installed Dimension drawings 159 ...
Page 160: ...Frame R2 Frame R2 front side IP20 UL open type 160 Dimension drawings ...
Page 161: ... Frame R2 bottom rear IP20 UL open type Dimension drawings 161 ...
Page 162: ... Frame R2 front side UL Type 1 kit installed 162 Dimension drawings ...
Page 163: ... Frame R2 bottom rear UL Type 1 kit installed Dimension drawings 163 ...
Page 164: ...Frame R3 Frame R3 front side IP20 UL open type 164 Dimension drawings ...
Page 165: ... Frame R3 bottom rear IP20 UL open type Dimension drawings 165 ...
Page 166: ... Frame R3 front side UL Type 1 kit installed 166 Dimension drawings ...
Page 167: ... Frame R3 bottom rear UL Type 1 kit installed Dimension drawings 167 ...
Page 168: ...Frame R4 Frame R4 front side IP20 UL open type 168 Dimension drawings ...
Page 169: ... Frame R4 bottom rear IP20 UL open type Dimension drawings 169 ...
Page 170: ... Frame R4 front side UL Type 1 kit installed 170 Dimension drawings ...
Page 171: ... Frame R4 bottom rear UL Type 1 kit installed Dimension drawings 171 ...
Page 172: ...172 ...
Page 180: ...180 ...
Page 198: ... Declaration of conformity 198 The Safe torque off function ...
Page 206: ...Dimensions 206 BIO 01 I O extension module ...
Page 212: ...Dimensions 3AXD50000031148 rev A 212 BREL 01 relay output extension module ...