Name
Value
Internal value
Internal value,
type
Default
Input delay
8 ms
8 ms
BYTE
8 ms
Fast counter
0
:
10
3
)
0
:
10
BYTE
0
Detect short cir-
cuit at outputs
On
1
BYTE
On
Behavior digital
outputs at comm.
error
Off
0
BYTE
Off
Substitute value
digital outputs
0
0..255
BYTE
0
Overvoltage
behavior on
output
Off
0
BYTE
Off
Behavior analog
outputs atcomm.
error
Off
0
BYTE
Off
I/O-Bus reset
Off
0
BYTE
Off
On
1
BYTE
Off
Remarks:
1
)
With a faulty ID, the modules reports a "parameter error" and does not perform
cyclic process data transmission.
2
)
As for device index C0 the parameter is no longer evaluated.
3
)
Counter operating modes, see description of the Fast counter
1.6.1.2.9 “Fast counter” on page 349
Table 166: Error LED / Failsafe function
Setting
Description
On
Error LED (S-ERR) lights up at errors of all
error classes, Failsafe-mode off
Off by E4
Error LED (S-ERR) lights up at errors of error
classes E1, E2 and E3, Failsafe-mode off
Off by E3
Error LED (S-ERR) lights up at errors of error
classes E1 and E2, Failsafe-mode off
On +Failsafe
Error LED (S-ERR) lights up at errors of all
error classes, Failsafe-mode on *)
Off by E4 + Failsafe
Error LED (S-ERR) lights up at errors of error
classes E1, E2 and E3, Failsafe-mode on *)
Off by E3 + Failsafe
Error LED (S-ERR) lights up at errors of error
classes E1 and E2, Failsafe-mode on *)
*) The parameters Behaviour AO at comm. error and Behaviour DO at comm. error are only
analyzed if the Failsafe-mode is ON.
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/31
3ADR010278, 3, en_US