Section 3 Configuration
Powering Units in the Cabinet
3BSE 027 941 R301
103
Powering Units in the Cabinet
This power supply is only connected to units within the cabinet such as:
•
PM8xx, which also powers all communication interfaces (via the CEX-bus)
and all S800 I/O units connected to its electrical ModuleBus.
•
TB820V2/TB840 (optical modem for S800 I/O) which also powers all S800
I/O units connected to its electrical ModuleBus.
•
CI830 (PROFIBUS DP interface for S800 I/O) which also powers all S800 I/O
units connected to its electrical ModuleBus.
•
PROFIBUS DP and PROFIBUS DP-V1 adapters for other I/O systems
(depending on the supply arrangement for the I/O units, it may be necessary to
connect power to each I/O unit).
•
Communication modems located in the cabinet.
The main configuration rule for this power supply is to retain the 24 V cables within
the cabinet.
Powering Field Equipment outside the Cabinet
This is intended for supplying power to process signals and equipment located
outside the cabinet.
Interference
Powering field equipment from a power supply located in the AC 800M Controller
cabinet often requires the use of long 24 V DC cables that can easily pick up local
interference and direct it straight back to the power supply units. When installing the
cables follow the Field Cables, given under
Short circuit at the power supply output
The SD82x series power supply has no extra energy reservoir at its outputs. In the
event of a short circuit the power supply output voltage will fall rapidly.
Short circuits (even with fuses installed in the 24 V DC distribution system) or large
load changes can produce unwanted voltage dips in supply.
Summary of Contents for AC 800M
Page 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Page 2: ......
Page 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Page 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Page 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Page 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Page 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Page 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Page 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Page 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Page 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Page 228: ...QGH 228 3BSE 027 941 R301...
Page 229: ......