Section 2 Functional Description
Status Handling for DeviceNet Slaves
9ARD000014-600 A
37
Status Handling for DeviceNet Slaves
shows all DeviceNet slave specific Unit Status bits in ErrorAndWarnings.
Table 6. Errors and Warnings of DeviceNet Device
Bit
Value
Text
Indication
Alarm/Event
Severity
Description
31
0x80000000
Device Not
Found
Warning
Alarm
High
Set when
DeviceNet device
is removed from
network or it is not
accessible.
30
0x40000000
Wrong
Device Type
Warning
Alarm
High
Set if the
electronic Key is
enabled for
DeviceNet device
and its Identity
Information is not
matching with the
device in network.
29
0x20000000
Internal
Config Error
Warning
-
-
Set when the
configuration
requests, to
configure
DeviceNet device,
fails.
28
0x10000000
Connection
Timed Out
Warning
Alarm
High
Set when
Connection with
the DeviceNet
device is not
Timed out
27
0x08000000
Duplicate
MAC Id
Error
Warning
Alarm
High
Set when another
DeviceNet device
found at the same
MAC id.
Summary of Contents for AC 800M
Page 2: ......
Page 3: ...AC 800M EtherNet IP DeviceNet Configuration System Version 6 0 ...
Page 10: ...Table of Contents 10 9ARD000014 600 A ...
Page 18: ...Released User Manuals and Release Notes About This User Manual 18 9ARD000014 600 A ...
Page 22: ...Figure 1 System configuration Device Import Wizard Section 1 Introduction 22 9ARD000014 600 A ...
Page 26: ...Linear Network Section 1 Introduction 26 9ARD000014 600 A ...
Page 46: ...Hot Swap of EtherNet IP Device Section 2 Functional Description 46 9ARD000014 600 A ...
Page 68: ...Figure 22 Enum Values File Section 3 Device Import Wizard 68 9ARD000014 600 A ...
Page 71: ...Section 3 Device Import Wizard File 9ARD000014 600 A 71 Figure 25 EDS Range selection ...
Page 222: ...Auxiliary RS 232 9 Pin D Subminiature Section 8 Hardware Connections 222 9ARD000014 600 A ...
Page 259: ......