Data
Value
Input v30 V
Replacement device: < 8 mA
Existing device:
£
9 mA
Maximum cable length:
-> Shielded
1000 m
-> Unshielded
600 m
Protection against reversed voltage
Yes
Overvoltage protection
Up to 30 V DC
*) Input delay of the S500 module DC532. The transmission rate via serial buses has not been
taken into account.
For further information, please refer to the existing documentation
System description Advant Controller 31.
1.5.1.8.3 Technical Data of the Digital Outputs
Data
Value
Connections
X5/3.0, X5/3.1, X5/3.2, X5/3.3, X5/3.4, X5/3.5,
X5/3.6, X5/3.7
Type of digital outputs
High-side switch
Demagnetization with inductive load
With a varistor inside the device (with other
circuitry)
Switching frequency with ohmic load
On request
Output voltage at signal 1
X4 / L+ (typ. 24 V) -0.8 V
Output delay: 0 -> 1 or 1 -> 0
On request
Maximum cable length:
-> Shielded
1000 m
-> Unshielded
600 m
For further information, please refer to the existing documentation
System description Advant Controller 31.
1.5.1.8.4 Technical data of the configurable inputs/outputs
Data
Value
Connections
X6/4.0, X6/4.1, X6/4.2, X6/4.3, X6/4.4, X6/4.5,
X6/4.6, X6/4.7
Use as digital input
See
Chapter 1.5.1.8.2 “Technical Data of
the Digital Inputs” on page 69
Use as digital output
See
Chapter 1.5.1.8.3 “Technical Data of
the Digital Outputs” on page 70
AC31 Adapters
Replacement devices: I/O modules > Replacement device 07DC91-AD
2018/09/24
3ADR010122, 8, en_US
70