Document all the recorded data from the IED before resetting the
tripping and lockout functions.
4.4.3
Monitoring fault records
Timestamps of the fault records are shown as a list.
1. Select Fault records in the View bar.
The fault records stored in the IED's memory are listed. The first fault record is
the newest. Select View all to view all fault records.
2. You save the fault records either as a text (.txt) or comma separated value (.csv)
file.
3. You can clear all fault records from the IED's memory by selecting Clear records.
4.4.4
Monitoring events
Event view contains a list of events produced by the application configuration. Each
event takes one view area. The header area shows the currently viewed event index
and the total amount of the events. The most recent event is always first.
1. Select Events in the View bar.
Figure 33: Events view
Number of events displayed can be selected. Gathering of event data can be
stopped temporarily by selecting Freeze.
2. Save the event data as a text (.txt) or comma separated value (.csv) file. Select
Export to save event information.
3. Clear all event data from the IED's memory by selecting Clear events.
IED operation
1MRS758850 D
52
SSC600
Operation Manual