MOD Group Displays
Section 3 CCF Displays
62
3BUR002418-600 A
MOD Group Displays
A group is a collection of related loops. Generally, a group has up to 12 control
loops or up to 36 indicator loops or a combination of both. Control loops assigned to
indicator targets provide limited information and cannot be used for control.
Monitoring and control functions (control is enabled in the MOD Group Object) are
provided in the Group Status and Group Trend displays. A custom graphic can be
configured for the Group Graphic display. The Group Alarm display is a filtered list
of a selected event group page.
Group Status Display
The Group Status Display,
, shows the current status of all tags within the
group by organizing the tags into status blocks (one per control loop, and up to three
indicator loops). Trend data is shown for PID and A/M control loops which have
trending configured in the database. Device loop status blocks show tag, descriptor,
command state, mode, and state. Indicator loop status blocks show basic
information for up to three tags.
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......