Controller Node Subsystem Status Display
Section 6 Status Displays
132
3BUR002418-600 A
immediately after the request to confirm is the request executed. You can select
Cancel
at any time to abort a request that has not yet been confirmed.
A Control Card redundancy request is initiated by selecting the status block for the
desired Control Module. (The block is highlighted to show selection.) Next, you
select the
Redundancy Request
button to bring up a set of commands described
below:
Establish Redundancy
- Establishes redundancy.
Terminate Redundancy
- Also terminates the Redundancy Auto-Establish
mode.
Start Controller
- Used to get out of the READY state.
Hard Reset
- Causes the Control Module to reset. This command is similar to
pulling the Control Module out of the slot and then re-inserting it.
Fail Over
- Requests fail over of the Primary Control Module to the Backup
Control Module. If the fail over is unsuccessful, the Primary Control Module
continues to function as if no request to fail over occurred.
Switch Back
- Requests switch back from the Backup Control Module to the
Primary Control Module.
Confirm
- Confirms and sends request to the subdevice.
Cancel
- Cancels any request not yet confirmed.
When one of the above commands is selected (except
Confirm
and
Cancel
), the
request and the subdevice number are shown and a prompt is displayed requesting
confirmation of the selected action. If the action and selected module are correct,
then select
Confirm
. Otherwise, select a different action and/or module.
Controller Subsystem Status Display Requests
The Display Request button is used to access a
LAN display or a Controller I/O (
) display
(only one or the other can be available). First select an
available controller, then select the Display Request
button and then select the appropriate display.
Alternately, you can select a specific Remote I/O or
Direct I/O in the Diagnostic area.
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......