![ABB A255-L35 Original Operation Manual Download Page 113](http://html.mh-extra.com/html/abb/a255-l35/a255-l35_original-operation-manual_903113.webp)
Operation Manual / 4 Product description / A200-L
8 Disassembly and assembly / 8.19 Fitting the diffuser
© Copyright 2020 ABB. All rights reserved.
HZTL4036_EN
Rev.R
October 2020
8.19
Fitting the diffuser
Fig. 55: Fitting the diffuser
Product
Size
Tightening torque [Nm]
A255-L
M5
6
A260-L
M5
6
A265-L
M5
6
A270-L
M6
10
A275-L
M8
25
A280-L
M8
25
Table 38: Tightening torque (77015)
1. Attach lifting gear (L) to the diffuser (79000).
2. Carefully place the diffuser on the wall insert (77000), then remove lifting gear.
3. Fit new O-rings (79020, 79021) on the diffuser.
4. Degrease screws (77015) and threaded holes in wall insert.
5. Coat threads of the screws with Loctite® 542.
6. Fit screws.