ABB 88TK50-E/R1210 Module And Application Description Download Page 2

88TK50/R1210

2

PROCONTROL remote---bus coupling

Sending from the station

For send data communication, the station protocol control

offers two modes:

Cyclic mode

Event mode.

In cyclic mode, the station protocol control allocates the send

permit (activated by cyclic calls) to the station modules, one

after the other, allowing them to send their cyclic telegrams

which are then stored in the send shared memory by the

station---bus interface.
At intervals of approx. 30 msec, the FDDI system interface

sends the cyclic telegrams available in the send shared

memory, packed in FDDI frames, with broadcast addressing to

the FDDI ring via the standard interface.
The number of telegrams to be transmitted per time interval is

calculated by the 88TK50 based on the system parameters

and the number of cyclic send telegrams from the station.
In event mode, the station protocol control (activated by event

calls) grants a send permit to those modules, which have indi-

cated an event, allowing them to send their event telegrams.

These telegrams will be stored by the station---bus interface in

the event---send FIFO. Entries in the event---send FIFO simul-

taneously update the entries in the cyclic send shared

memory.
Within the token rotation time of the FDDI token, the FDDI sys-

tem interface then sends the event telegrams available in the

event---send FIFO, packed in FDDI frames with broadcast

addressing, to the FDDI ring via the standard interface.
During this procedure, all telegrams are checked for accuracy

as to formal criteria and to their contents after they have been

transferred over the station bus.
In the case of a fault, the telegram is inhibited through the

station---bus protocol control and, consequently, not sent onto

the FDDI ring.

Sending to the station

The module receives all PROCONTROL telegrams, packed in

FDDI frames which are transferred over the FDDI ring.
The FDDI data unit of a received frame determines, whether

and in which receive shared memory the telegrams packed in

the frame shall be made available to the station---bus interface

for sending.
FDDI frames with packed event telegrams will be given priority.
When the event data are being distributed, the cyclic PRO-

CONTROL receive shared memory for cyclic data is updated

immediately so that no previous values will be transmitted

when distribution from the cyclic receive shared memory is

resumed.

A distinction is being made between FDDI frames with broad-

cast addressing and ones with destination addressing.

Telegrams with process data are transmitted by means of

FDDI frames with broadcast addressing. Telegrams with list

data are transmitted by means of FDDI frames with destination

addressing.

This means that list data are received only in stations with the

respective destination address.

The FDDI system interface unpacks the telegrams and makes

the cyclic telegrams in the cyclic receive shared memory, the

event telegrams in the event---receive FIFO and the list tele-

grams in the list---receive shared memory available to the

station---bus interface for sending.

The cyclic telegrams in the cyclic receive shared memory are

made available station---by---station one after the other which

means that the cyclic telegrams will also be sent station---by---

station over the station bus.

The formal accuracy of the received FDDI frames is checked

based on a frame check sequence which is used to secure the

telegrams packed in the FDDI frames.

If any error is detected in an FDDI frame addressed to the

station, the telegrams of this frame will not be stored in the

receive shared memory. The FDDI system interface, however,

will initiate the following by setting the fault flag in the frame

status field:

--- In the case of a frame with event telegrams, the faulty

frames received are repeated,

--- In the case of a frame with cyclic telegrams, a new cyclic

frame with the current data of the station will be transmitted.

The station---bus interface sends the telegrams filed in the

receive shared memories over the station bus, the event

telegrams taking priority.

On that occasion, formal accuracy of the telegrams is checked

based on the check characters protecting the telegram

contents (operation code, addresses, data) by the receiving

modules.

If an error has been detected, these telegrams will not be eval-

uated.

The station cycle starts with a ’start cycle’ telegram and ends

with the ’start cycle’ telegram of the next one.

The ’start cycle’ telegram is generated by the 88TK50 after all

cyclic send telegrams and all receive telegrams have been

transferred once within the station.

Due to the interruptions caused by the transmission of event

telegrams and list telegrams, the length of a station cycle is

determined by the number of cyclic send telegrams of that

specific station and of the other stations as well as by the

number of event telegrams and list telegrams to be trans-

ferred.

Summary of Contents for 88TK50-E/R1210

Page 1: ...module is equipped with Two standard interfaces for the station bus One standard interface with the FDDI ring based on ISO IEC 9314 One interface for dual channel station bus coupling via a second coupling module One potential isolated monitoring interface for cabinet annunciations One test and service interface One potential isolated input for deactivating the optical transceivers The module uses...

Page 2: ...e cyclic receive shared memory is resumed A distinction is being made between FDDI frames with broad cast addressing and ones with destination addressing Telegrams with process data are transmitted by means of FDDI frames with broadcast addressing Telegrams with list data are transmitted by means of FDDI frames with destination addressing This means that list data are received only in stations wit...

Page 3: ... mode transmission of the event telegrams of all modules in a station Cyclic distribution mode transmission of the send tele grams received over the FDDI Event distribution mode transmission of the event tele grams received over the FDDI List mode transmission of the list telegrams Address transmission The system and station addresses of a PROCONTROL station are set on the 88TK50 module In the ope...

Page 4: ...dress 60 must be selected In the case of dual channel station coupling both 88TK05 modules must have the same station addresses system ad dresses and operating modes however different module ad dresses 60 61 need to be set The station and system address settings are transmitted in a telegram to all modules of the PROCONTROL station cf para graph on Station protocol control address transmission Inc...

Page 5: ...g the cabinet power supply This monitoring function allows to detect whether the power supply for the station modules has failed If input MSP is not used contact X21 z20 must be connected to Z and contact X21 b20 to USA and USB Input MTE uses the open circuit principle and is intended for instance for external cabinet temperature monitoring Input MTK uses the open circuit principle This input may ...

Page 6: ...e disturbance annunciation signals of the module via the PROCONTROL remote bus FDDI interface They also include message General disturbance of station detected generated from the individual signals of the station modules The 88TK50 transmits its disturbance annunciation signals and diagnosis results in 2 diagnosis registers using register address 246 The contents of both diagnosis registers are tr...

Page 7: ...rams of the station are being transmitted over the FDDI ring Light emitting diode SZ is illuminated for approx 100 msec when a new station cycle starts Light emitting diode SV is illuminated when the send tele grams of the station are being transmitted over the station bus Light emitting diode ER is illuminated from the moment when events have been detected until the event telegrams are being tran...

Page 8: ... Transmit allocation in AS missing Checksum error detected 7 6 S S 1 4405 4404 4400 4403 4409 4410 4402 4406 4407 Processor halt Voltage monitoring responded Bus coupling module Wrong firmware PROM Hardware defect messages 2 1 Only in the case of dual channel station bus coupling S Static annunciations disappear automatically upon deactivation D Dynamic annunciations are cancelled after the conten...

Page 9: ...e address code A 0 60 B 1 61 Protocol error AS detected 4430 4412 4415 4419 4417 S messages SSG Voltage monitoring responded not accessible from bus Wrong firmware PROM Hardware defect 0 Not used For cause and associated module address cf background diagnosis register Figures 3 to 5 For cause cf background diagnosis register Figures 3 to 5 Operating mode setting wrong 4423 Station mod arrangem cha...

Page 10: ...gnosis register D Background Module address decimal of module not responding after being granted a send permit twice Counter of number of cycle abortions 129 Cause for Response from module missing 62 246 1 when module address 60 is set 145 Cause for Response from module missing 62 246 1 when module address 61 is set 131 Cause for Cycle abortion detected 62 246 3 when module address 60 is set 147 C...

Page 11: ...7 6 5 4 3 2 1 0 Type 0 0 0 0 0 0 0 0 0 0 D S S 0 0 diagnosis register 0 Background No start cycle telegram received 132 Cause for Telegram error in AS detected 62 246 4 when module address 60 is set 148 Cause for Telegram error in AS detected 62 246 4 when module address 61 is set 135 Cause for Operating mode setting wrong 62 246 7 when module address 60 is set 151 Cause for Operating mode setting...

Page 12: ...0 0 0 0 0 0 0 0 0 0 S 0 S S S diagnosis register Wrong station system address setting Wrong module address setting 60 61 0 Background Hardware defect Discrepancy of operating mode setting 136 Cause for Module from AS bus disconnected 62 246 8 when module address 60 is set 152 Cause for Module from AS bus disconnected 62 246 8 when module address 61 is set 139 Cause for Partner module fault 62 246 ...

Page 13: ...D D D D D D D D D diagnosis register Telegram contents not plausible Protocol violation 0 Background Module address decimal of last send permit 141 Cause for Response from module missing 62 246 1 when module address 60 is set 157 Cause for Protocol error AS detected 62 246 13 when module address 61 is set Figure 6 Background diagnosis registers 141 and 157 are read using module address 62 ...

Page 14: ...ation bus coupling Station bus 88TK50 Station bus 88TK50 X2 X3 X2 X3 FDDI Ring 1 Ring 2 FDDI Ring 1 Ring 2 max 2 km Dual channel station bus coupling Station bus FDDI Ring 1 Ring 2 88TK50 X2 X3 88TK50 X2 X3 Station bus 88TK50 X2 X3 88TK50 X2 X3 max 2 km FDDI Ring 1 Ring 2 ...

Page 15: ...8 Standard interface Station bus Station protocol control Interface for dual channel Station bus 88TK50 E R1210 station bus coupling Diagnosis and annunciation functions Monitoring interface Setting z18 ZM z20 ZM z22 ZM X21 b28 MST BA X11 X12 Station bus interface Send shared memory event send FIFO Receive shared memory event receive FIFO GND b02 GND b12 TX b06 RX b08 TX d06 RX d08 GAI d12 X21 4 V...

Page 16: ...View of connector side X 11 X 21 X 12 X 22 Printed circuit board 1 Printed circuit board 2 Contact assignments of connector X1 1 GND 2 V24T1 3 V24R1 4 V24T2 5 V24R2 6 TX 7 TX 8 RX 9 RX Contact assignments of connector X21 View of contact side d b z 02 BYOUT GND GND 04 06 TX TX GND 08 RX RX GND 10 12 GAI GND 14 16 18 UM ZM 20 MSP ZM 22 MTE ZM 24 MTK ZM 26 MSX ZM 28 MST ZM 30 32 ESP ZE Contact assig...

Page 17: ... FS X1 X3 X3 1 8 4 5 6 7 2 3 ON 1 8 4 5 6 7 2 3 ON Not used 1 2 A720 A710 3 4 A740 A730 5 6 A760 A750 S700 S701 Memory modules Order number EPROM programmed 1 A710 GJR2397061Pxxxx 2 A720 GJR2397062Pxxxx 3 A730 GJR2397063Pxxxx 4 A740 GJR2397064Pxxxx 5 A750 GJR2397065Pxxxx 6 A760 GJR2397066Pxxxx Remarks on single PROMs Under the order no for the complete module the complete set of memory modules for...

Page 18: ...printed circuit board 1 X11 X21 X1 1 2 A23 A24 A12 3 Memory modules Order number Flash PROM programmed 1 A23 GJR2397042Pxxxx 2 A24 GJR2397043Pxxxx 3 A12 GJR2397041Pxxxx xxxx Position number indicating the applicable program version ...

Page 19: ...ke Transmission distance Up to 15 m without line amplifier FDDI interface acc to ISO IEC 9314 Application Connecting the PROCONTROL station to the PROCONTROL remote bus Transmission protocol FDDI protocol with a token rotation time of 3 msec Transmission rate 100 Mbit sec Transmission mode Synchronous and asynchronous non restricted token Type of connection Single MAC DAS Transmission distance bet...

Page 20: ...s shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction in whole or in parts is forbidden without ABB s prior written consent Copyright 2009 ABB All rights reserved ABB AG Power Technology Systems P O B...

Reviews: