Sodium Monitoring in Water Treatment Processes

AG/AI-024_4

4

Process Description

Basic Measurement/ Analysis Theory

All on-line sodium monitors are based on the use of a sodium ion selective
electrode and a reference electrode. The measurement is very similar to that of pH,
with the electrode pair also responding to hydrogen ions and changes in sample
temperature.

The hydrogen ion interference is controlled by raising the pH of the sample
(reducing the hydrogen ion concentration). This is achieved by adding an alkali
– usually ammonia gas or a volatile amine. Temperature effects are reduced by
monitoring temperature and carrying out automatic temperature compensation.
The monitor is calibrated by use of solutions of known sodium ion concentration,
with the electrode pair producing a millivolt output proportional to the sodium
ion concentration.

Cation Exchange Bed

Cations are exchanged for hydrogen ions in this bed until all the hydrogen
ions in the bed have been removed. At this stage (known as resin bed
exhaustion) the levels of dissolved solids in the water will increase and
the resin will need to be regenerated by passing acid (usually sulphuric
or hydrochloric) to reinstate the hydrogen ions in the resin.

Mixed Bed

The mixed bed contains a mixture of both cation and anion exchange resins
to further reduce the dissolved solids content, and thus produce the quality
of make

-

up water required.

Condensate Polishing Plant (CPP)

This type of plant is used mainly on once

-

through type boilers. It takes the

condensate from the steam turbine/condenser and purifies or polishes it to
reduce the concentrations of any impurities such as sodium chloride, sulphate
etc., which may have entered the system via condenser tube leaks. Condensate
polishing plants (CPP's – see figure on previous page) only normally remove
small levels of contaminants, therefore only have a mixed bed stage.

Measuring Points

Cation Bed Outlet

Monovalent cations such as sodium (Na

+

) are the first ions to breakthrough when

cation resin exhaustion occurs. The ability of the sodium monitor to detect very
low levels of sodium makes it a much more sensitive method of detecting resin
exhaustion than conductivity.

Mixed Bed Outlet

Here again, sodium monitors are used to check the quality of the final water
and detect exhaustion of the cation exchange resin within the mixed bed. It is
essential that the sodium concentration in the final water is kept as low as
possible to minimize thermal losses due to blowdown

.

Condensate Polishing Plant (CPP) Outlet

As with the complete demineralisation plant, the CPP has a sodium monitor on
the outlet from the mixed bed unit to detect exhaustion of the cation resin. This is
particularly important on once

-

through boilers as any sodium in the feed water

after the CPP is deposited in the boiler, causing corrosion and potentially, the premature
shutdown of the system.

Summary of Contents for 8037

Page 1: ...8037 Sodium Monitor Typical Range 0 1ppb to 10ppm Normal sodium concentration 100ppb dependent upon type of exchange and raw water quality 8037 Sodium Monitor Typical Range 0 01ppb to 1 0ppm Normal sodium concentration 1 0ppb Sample to sodium Monitor Sample to sodium Monitor The illustration above shows a simple demineralisation plant where anions are exchanged with hydroxyl ions and cations are e...

Page 2: ...onal maintenance normally required by such systems We supply full details of reagents to ensure the most cost effective procurement options Our integral constant head design eliminates the effects of sample pressure and flow rate variations and minimises sample transport time Our patented calibration solution technique ensures thermal equilibrium In addition ABB offer greater security at a lower c...

Page 3: ...nt Plant on a rack preferably in an air conditioned room Samples are normally at ambient temperatures so sample cooling should not be necessary even the polishing plant will be below 55 C Fit a needle valve upstream to control the sample flow within required limits Conveniently site the standard solution bottles on the top of the liquid handling section of the monitor Simplified schematic of once ...

Page 4: ...solids content and thus produce the quality of make up water required Condensate Polishing Plant CPP This type of plant is used mainly on once through type boilers It takes the condensate from the steam turbine condenser and purifies or polishes it to reduce the concentrations of any impurities such as sodium chloride sulphate etc which may have entered the system via condenser tube leaks Condensa...

Page 5: ... County Line Road Warminster PA 18974 USA Tel 1 215 674 6000 Fax 1 215 674 7183 ABB has Sales Customer Support expertise in over 100 countries worldwide www abb com The Company s policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice Printed in UK 12 03 ABB 2003 ...

Reviews: