Section 7
1MAC050144-MB C
Control functions
532
615 series ANSI
Technical Manual
The last change of the emergency start output signal is recorded.
7.4.6
Signals
Table 436: 62EST Input signals
Table 437: 62EST Output signals
7.4.7
Settings
Table 438: 62EST Group settings
Table 439: 62EST Non group settings
7.4.8
Monitored data
Table 440: 62EST Monitored data
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
ST_EMERG_RQ
BOOLEAN
0=False
Emergency start input
Name
Type
Description
ST_EMERG_ENA
BOOLEAN
Emergency start
Parameter
Values (Range)
Unit
Step
Default
Description
Motor standstill A
0.05...0.20
xIn
0.01
0.12
Current limit to check for motor standstill condition
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable5=Disable
1=Enable
Operation Disable / Enable
Name
Type
Values (Range)
Unit
Description
T_ST_EMERG
Timestamp
Emergency start activation timestamp
62EST
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......