![ABB 2CSM110000R1011 Assembly And Operating Instructions Manual Download Page 19](http://html.mh-extra.com/html/abb/2csm110000r1011/2csm110000r1011_assembly-and-operating-instructions-manual_4284019.webp)
15
Instructions for the assemblage and the use
3. Technical characteristics
Power supply voltage
[V]
230 AC ±10%
Frequency
[Hz]
50/60
Max input signal value
EMT
[A]
25 AC
AMTD-1, AMTD-1-R
[A]
5 AC
VLMD-1-2,VLMD-1-2-R [V]
600 AC/DC
AMTD-2, AMTD-2-R
[mV]
60 DC
FRZ-DIG
[Hz]
80
Full scale values available
on AMTD-1 and AMTD-1-R
[A]
Direct insertion by means of CT …/5A
15 20 25 40 60 100 150 200 250 400 600 999
Full scale values available
on AMTD-2 and AMTD-2-R
[A]
Indirect insertion by means of shunt 60mV
15 20 25 40 60 100 150 200 250 400 600 999
Transformation ratio settings
available for EMT
60/5, 100/5, 250/5, 600/5, 800/5, 1000/5,
Measurement range
EMT
[kWh]
0…9999 AC
AMTD-1, AMTD-1-R
[A]
0…999 AC
VLMD-1-2,VLMD-1-2-R [V]
0…600 AC/DC
AMTD-2, AMTD-2-R
[A]
0…999 DC
FRZ-DIG
[Hz]
40…80
Accuracy class
EMT
Class 2
AMTD-1, AMTD-1-R
[%]
0,5 ±1 digit
AMTD-2, AMTD-2-R
[%]
0,5 ±1 digit
VLMD-1-2, VLMD-1-2-R [%]
0,5 ±1 digit
FRZ-DIG
[%]
0,5 ±1 digit
EN
Summary of Contents for 2CSM110000R1011
Page 2: ...1 2 3 4 5 6 7 8 9 10 11 12 52 5 50 3 64 8 45 58 85 mm 1 2 1 2 DIN EN 50022 35 mm ...
Page 21: ...17 Instructions for the assemblage and the use EN ...
Page 37: ...17 Istruzioni per il montaggio e l uso IT ...
Page 53: ...17 Montageanleitung D ...
Page 69: ...17 Instructions pour le montage et l utilisation F ...
Page 85: ...17 Instrucciones de montaje ES ...
Page 101: ...17 Instruções de montagem P ...
Page 117: ...17 Οδηγίες χρήσης GR ...
Page 118: ......