Mounting / Installation 

 

Pos: 33 /Busch-Jaeger (Neustruktur)/Modul-Struktur/Online-Dokumentation/Sicherheit (--> Für alle Dokumente <--)/Warnhinweise/Sicherheit - Niederspannungs- und 230 V-Leitungen @ 18\mod_1302617821491_15.docx @ 103465 @  @ 1 

 

 

 

Warning 

E lec tric  voltage!  

Risk of death and fire due to electrical voltage of 230 V. 
–  Low-voltage and 230 V cables must not be installed together in a flush-mounted socket! 
 

In case of a short-circuit there is the danger of a 230 V load on the low-voltage line. 

 
 

Pos: 34 /Busch-Jaeger (Neustruktur)/Modul-Struktur/Online-Dokumentation/Sicherheit (--> Für alle Dokumente <--)/Warnhinweise/Sicherheit - Fachkenntnisse @ 18\mod_1302774384017_15.docx @ 103564 @ 2 @ 1 

 

7.1

 

R equirements  for the elec tric ian 

 

 

 

Warning 

E lec tric   voltage!  

Install the device only if you have the necessary electrical engineering knowledge and experience. 

 

Incorrect installation endangers your life and that of the user of the electrical system. 

 

Incorrect installation can cause serious damage to property, e.g. due to fire. 

 
The minimum necessary expert knowledge and requirements for the installation are as follows: 

 

Apply the "five safety rules" (DIN VDE 0105, EN 50110):  

 

1. 

Disconnect from power;  

 

2. 

Secure against being re-connected;  

 

3. 

Ensure there is no voltage;  

 

4. 

Connect to earth; 

 

5. 

Cover or barricade adjacent live parts. 

 

Use suitable personal protective clothing. 

 

Use only suitable tools and measuring devices. 

 

Check the type supply network (TN system, IT system, TT system) to secure the following 
power supply conditions (classic connection to ground, protective earthing, necessary 
additional measures, etc.). 

 
 

Pos: 35 /DinA4 - Anleitungen Online/Inhalt/KNX/DoorEntry/Montage/Montagehinweise - Allgemein @ 19\mod_1310563670478_15.docx @ 107743 @ 2 @ 1 

 

7.2

 

G eneral ins tallation ins truc tions  

 

 

Terminate all branches of the wiring system via a connected bus device (e.g., indoor station, outdoor station, 
system device). 

 

Do not install the system controller directly next to the bell transformer and other power supplies (to avoid 
interference). 

 

Do not install the wires of the system bus together with 230 V wires. 

 

Do not use common cables for the connecting wires of the door openers and wires of the system bus. 

 

Avoid bridges between different cable types. 

 

Use only two wires for the system bus in a four-core or multi-core cable. 

 

When looping, never install the incoming and outgoing bus inside the same cable. 

 

Never install the internal and external bus inside the same cable. 

Pos: 36 /Busch-Jaeger (Neustruktur)/Modul-Struktur/Online-Dokumentation/Steuermodule - Online-Dokumentation (--> Für alle Dokumente <--)/++++++++++++ Seitenu+++++++++++ @ 9\mod_1268898668093_0.docx @ 52149 @  @ 1 

 

 

 

Summary of Contents for 2CKA008300A0080

Page 1: ...e Pos 2 DinA4 Anleitungen Online Inhalt KNX DoorEntry 83205 AP xxx Titelblatt 83205 AP xxx ABB 19 mod_1323162341195_15 docx 110844 1 83205 SM xxx 500 83205 SM xxx 515 Indoor audio station with handset Ende der Liste für Textmarke Cover ...

Page 2: ...d settings 6 5 2 2 Terminal resistor 7 5 2 3 Setting the master slave switch 8 6 Technical data 9 7 Mounting Installation 10 7 1 Requirements for the electrician 10 7 2 General installation instructions 10 7 3 Mounting 11 8 Addressing 14 8 1 Addressing the stations 14 8 1 1 Potentiometer 14 8 1 2 Setting the address of the outdoor station 14 8 1 3 Assigning the doorbell push button of an outdoor s...

Page 3: ...welt Hinweis Elektrogeräte 18 mod_1302763973434_15 docx 103500 1 C ons ider the protection of the environment Used electric and electronic devices must not be disposed of with domestic waste The device contains valuable raw materials which can be recycled Therefore dispose of the device at the appropriate collecting depot Pos 12 DinA4 Anleitungen Online Ueberschriften 2 ABB Geraete 19 mod_13231628...

Page 4: ...Inhalt KNX DoorEntry 83205 AP xxx Bedienung 83205 AP xxx 18 mod_1303207573139_15 docx 103616 33 1 5 1 1 A call is pending Lift off the handset to answer a call Fig 1 No Function 1 Press on the top push button to open the door 2 Press on the middle push button to switch on the lighting 3 Press on the bottom push button to switch off the bell 4 Press on the bottom push button to activate the mute fu...

Page 5: ...n to open the door 2 Press on the middle push button to switch on the lighting 3 Press on the bottom push button to refuse an incoming call Pos 20 Busch Jaeger Neustruktur Modul Struktur Online Dokumentation Steuermodule Online Dokumentation Für alle Dokumente Seitenumbruch 9 mod_1268898668093_0 docx 52149 1 ...

Page 6: ... tored s ettings Fig 3 No Function 1 Use this button to set the volume of the bell sound for the front door with the handset removed Five volume settings are available 2 Use this button to select the bell sound for the front door with the handset replaced Five bell sounds are available for selection 3 Use this button to set the volume of the bell sound for the floor door with the handset removed F...

Page 7: ...widerstand setzen 83205 AP xxx 19 mod_1310722802019_15 docx 107825 1 Fig 4 In pure audio installations always set the terminal resistor 2 on OFF In video installations or mixed audio and video installations set the terminal resistor for the the last devices of a branch on ON Pos 26 Busch Jaeger Neustruktur Modul Struktur Online Dokumentation Steuermodule Online Dokumentation Für alle Dokumente Sei...

Page 8: ... One station in each apartment must be set as Master All additional indoor stations in the same apartment must be set as Slave Indoor s tation that is to be s et as Mas ter Set the switch M 1 1 on ON F or all other indoor s tations Set the switch S 1 2 on OFF Pos 28 Busch Jaeger Neustruktur Modul Struktur Online Dokumentation Steuermodule Online Dokumentation Für alle Dokumente Seitenumbruch 9 mod...

Page 9: ...Daten 83205 AP xxx 18 mod_1303207574186_15 docx 103648 1 Des ignation Value Operating temperature 5 to 40 Storage temperature 20 C 70 C Protection IP 20 Single wire clamps 2 x 0 6 mm 2 x 1 mm Fine wire clamps 2 x 0 6 mm 2 x 0 75 mm Volume Maximum 80 dB Bus voltage 28 V 2 V Pos 31 Busch Jaeger Neustruktur Modul Struktur Online Dokumentation Steuermodule Online Dokumentation Für alle Dokumente Seite...

Page 10: ...llows Apply the five safety rules DIN VDE 0105 EN 50110 1 Disconnect from power 2 Secure against being re connected 3 Ensure there is no voltage 4 Connect to earth 5 Cover or barricade adjacent live parts Use suitable personal protective clothing Use only suitable tools and measuring devices Check the type supply network TN system IT system TT system to secure the following power supply conditions...

Page 11: ...of the indoor station by pressing in the clamp on the bottom of the device Pos 38 2 1 DinA4 Anleitungen Online Inhalt KNX DoorEntry Video Module Einleitungen Einleitung Zerlegen des Geraetes vor Geraetemontage 20 mod_1324553064982_15 docx 112573 1 Video for disassembling the device prior to mounting the device Pos 38 2 2 DinA4 Anleitungen Online Inhalt KNX DoorEntry Video Module Videos Sprachneutr...

Page 12: ...ice to the wall and connect it in accordance with the graphics The insulated section of the cable end must not be longer than 10 mm Fig 8 3 Set the address of the preferred outdoor stations and the address of the indoor station on the rotary switches see chapter Addressing on page 14 ...

Page 13: ... 1 DinA4 Anleitungen Online Inhalt KNX DoorEntry Video Module Einleitungen Einleitung Montage des Geraetes 20 mod_1324552679883_15 docx 112541 1 Video for mounting the device Pos 38 4 2 DinA4 Anleitungen Online Inhalt KNX DoorEntry Video Module Videos Sprachneutral Video Montage Innenstation Hoerer Montage Anschluss Aufsetzen 21 mod_1329749979538_0 docx 198643 1 Pos 39 Busch Jaeger Neustruktur Mod...

Page 14: ... actuators for door and light via the setting of the address For this the potentiometer house outdoors is set on an address between 1 and 4 The potentiometer is located on the rear of the outdoor station or the front of the MDRC switch actuator 8 1 3 As s igning the doorbell pus h button of an outdoor s tation to an apartment The doorbell push buttons of an outdoor station are assigned to the apar...

Page 15: ...tion must be set on the indoor stations For this the potentiometer STATION is set on the address of the standard outdoor station between 1 and 4 The potentiometer is located on the rear of the indoor stations Fig 12 Factory assignment of doorbell push buttons No Des ignation 1 Apartment 01 2 Apartment 01 3 Outdoor station 4 Apartment 09 5 Apartment 10 ...

Page 16: ...me Addressing 0073 1 7515 16 Fig 13 Several outdoor stations with identical assignment No Des ignation 1 Main entrance outdoor station 2 Side entrance outdoor station 3 Apartment 01 4 Apartment 02 5 Apartment 03 ...

Page 17: ... mod_1322130240851_15 docx 110503 2 1 8 2 Video for addres s ing the device Pos 43 1 DinA4 Anleitungen Online Inhalt KNX DoorEntry Video Module Einleitungen Einleitung Adressierung des Geraetes 20 mod_1324552270462_15 docx 112509 1 Video for addressing the device Pos 43 2 DinA4 Anleitungen Online Inhalt KNX DoorEntry Video Module Videos Sprachneutral Video Adressierung 21 mod_1329747104105_0 docx ...

Page 18: ... 45 DinA4 Anleitungen Online Inhalt KNX DoorEntry Projektierung Merkblatt Projektierung Merkblatt ABB 19 mod_1323176717034_15 docx 111044 1 Project name Mounting position for the outdoor station Floor 02 01 Ende der Liste für Textmarke Content ...

Page 19: ... We reserve the right to at all times make technical changes as well as changes to the contents of this document without prior notice The detailed specifications agreed to at the time of ordering apply to all orders ABB accepts no responsibility for possible errors or incompleteness in this document We reserve all rights to this document and the topics and illustrations contained therein The docum...

Reviews: