12 OI/266/FF-EN Rev. B
| 2600T Series Pressure transmitters
5 Mounting
5. Mounting
5.1 General
Study these installation instructions carefully before
proceeding. Failure to observe the warnings and instructions
may cause a malfunction or personal hazard. Before installing
the transmitter, check whether the device design meets the
requirements of the measuring point from a measurement
technology and safety point of view.
This applies in respect of the:
—
Explosion protection certification
—
Measuring range
—
Gauge pressure stability
—
Temperature
— Operating voltage
The suitability of the materials must be checked as regards
their resistance to the media. This applies in respect of the:
—
Gasket
— Process connection, isolating diaphragm, etc.
In addition, the relevant directives, regulations, standards, and
accident prevention regulations must be observed (e.g., VDE/
VDI 3512, DIN 19210, VBG, Elex V, etc.). Measurement
accuracy is largely dependent on correct installation of the
pressure transmitter and, if applicable, the associated
measuring pipe(s). As far as possible, the measuring setup
should be free from critical ambient conditions such as large
variations in temperature, vibrations, or shocks.
Important.
If unfavorable ambient conditions cannot be avoided for
reasons relating to building structure, measurement technology, or
other issues, the measurement quality may be affected. If a remote
seal with capillary tube is installed on the transmitter, the additional
operating instructions for remote seals and the related data sheets
must be observed.
5.2 IP protection & designation
The housings for 266 transmitters are certified as conforming
to protection type IP66 / IP67 (according tonIEC 60529) or
NEMA 4X (according to NEMA 250).
The first number indicates the type of protection the integrated
electronics have against the entry of foreign bodies, including
dust.
“6” means that the housing is dust-proof (i.e., no ingress of
dust). The second number indicates the type of protection
the integrated electronics have against the entry of water.
“6” means that the housing is protected against water;
specifically, powerful jets of water under standardized
conditions.
“7” means that the housing is protected against water;
specifically, against the effects of temporary immersion in
water under standardized water pressure and temporal
conditions.
5.3 Mounting the transmitter
5.3.1 Transmitter factory configuration consideration
The 266 pressure transmitter in your hands has been factory
calibrated to reflect the published declared performance
specification; no further calibration is required in normal
condition. ABB typically configures 266 pressure transmitters
according to the user requirements. A typical configuration
includes:
—
TAG number
—
Calibrated span
—
Output linearization
—
LCD display configuration
5.3.2 Hazardous area considerations
The transmitter must be installed in hazardous area only if it is
properly certified. The certification plate is permanently fixed on
the neck of the transmitter top housing. The 266 Pressure
Transmitter Line can have the following certifications:
ATEX INTRINSIC SAFETY
— II 1 G Ex ia IIC T4/T5/T6 and II 1/2 G Ex ia IIC T4/T5/T6
— II 1 D Ex iaD 20 T85°C and II 1/2 D Ex iaD 21 T85°C
ATEX EXPLOSION PROOF
— II 1/2 G Ex d IIC T6 and II 1/2 D Ex tD A21 IP67 T85°C
ATEX TYPE “N” / EUROPE:
— II 3 G Ex nL IIC T4/T5/T6 and II 3 D Ex tD A22 IP67 T85°C
COMBINED ATEX, ATEX FM and FM Canada
— See detailed classifications
FM Approvals US and FM Approvals Canada:
— Explosionproof (US): Class I, Div. 1, Groups A, B, C, D
— Explosionproof (Canada): Class I, Div. 1, Groups B, C, D
— Dust ignitionproof: Class II, Div. 1, Groups E, F, G
— Nonincendive: Class I, Div. 2, Groups A, B, C, D
— Intrinsically safe: Class I, II, III, Div. 1, Groups A, B, C, D,
E, F, G
— Class I, Zone 0, AEx ia IIC T6/T4 (FM US)
— Class I, Zone 0, Ex ia IIC T6/T4 (FM Canada)
IEC (Ex):
— See detailed classifications
INTRINSIC SAFETY/CHINA
— NEPSI approval
Ex ia IIC T4-T6
FLAMEPROOF/CHINA
— NEPSI approval
Ex d IIC T6
GOST (Russia), GOST (Kazakistan), Inmetro (Brazil)
— based on ATEX.
Summary of Contents for 266FF
Page 40: ...40 OI 266 FF EN Rev B 2600T Series Pressure transmitters 10 HMI local indicator Display ...
Page 41: ...2600T Series Pressure transmitters OI 266 FF EN Rev B 41 10 HMI local indicator ...
Page 42: ...42 OI 266 FF EN Rev B 2600T Series Pressure transmitters 10 HMI local indicator ...
Page 43: ...2600T Series Pressure transmitters OI 266 FF EN Rev B 43 10 HMI local indicator Device Info ...
Page 44: ...44 OI 266 FF EN Rev B 2600T Series Pressure transmitters 10 HMI local indicator Communication ...
Page 54: ...54 OI 266 FF EN Rev B 2600T Series Pressure transmitters ...
Page 55: ...2600T Series Pressure transmitters OI 266 FF EN Rev B 55 ...