E LEC TRON I C COM PAC T STA RTE R
| M A N UA L
R-type
The HMI of the R- device is described in chapter 1.10.3. The following figure 16 shows the corresponding drawing for the
device. Each box represents a functionality.
—
16 Circuit diagram of R- type
—
3.3
Setting the nominal current
For setting the nominal current, please proceed as outlined below:
1. Press the Reset / Set button for more than six sec. to change to setting mode. The green ‘PWR'-LED flashes once.
2. Set the nominal load current with the potentiometer. The nominal current is specified in 16 stages as shown in the
following table 5 Setting the nominal overload current and on the side of the device. The four LEDs signal the set current.
3. Store this value by pressing the Reset/ Set button again.
4. Press the Reset/ Set button for more than 2 sec. AND less than 6 sec. to display the set current (shown for 3 sec.). This
function is only possible if the device is not activated and there are no device errors.
Table 5 shows the nominal current codification that is applicable for all HF types.
Please note that the LEDs are switched off every two sec. for 0.3 sec. to distinguish this mode from other
operating modes.