Advant Controller AC 31 / Issued: 01.99
3 – 29
Technical specifications
3
3.7.3
TC50 display cables: 07 SK 54 and 07 SK 55
Refer to the TC 50 documentation supplied with the product.
3.7.4
Connectors (see Figure 13)
There are two other types of connectors available in addition to the removable connectors
supplied. They enable a simplified installation, where applicable.
1 – External dual connector: 07 ST 50
This connector is used to connect sensors or three wire digital actuators to the 40 and 50
series products.
All the terminal blocks of the same level are electrically connected.
2 – External dual connector: 07 ST 51
This connector permits the easy connection of analog sensors to the 40 and 50 series
products.
It includes a first level with 9 interlinked terminals. It may be used to connect the shielding of
the analog cables.
The second level (5 terminals) is used when the 4-wire probes are used. This connector
prevents a short circuit on a channel from disturbing the operation of the other channels.
An example of the cabling of a 4-wire probe to an XM 06 B5 analog unit using a dual connector
can be found in chapter 4.
Figure 13: Dual connectors 07 ST 50 and 07 ST 51