ELECTRICAL INSTALLATION
Fig. 5.2 AK104 System Diagram
Note 1
Apparatus which is unspecified except that it must not be supplied fr
om nor contain in norma
l
or abnormal conditions a sour
ce of potential with r
espect to earth in excess of 250 v
olts r
.m.s
or 250 volts d.c.
Note 2a
The capacitance and either the inductance or the inductance to r
esistance (L/R) ratio of
the
cable connected between the + and – terminals of the power supply T
ype 4234500/501 and
terminals 1 and 4 of a kathar
ometer T
ype 0065XX must not exceed the following values:
Gr
oup
Capacitance
in
μ
F
Inductance
in mH
L/R ratio
in
μ
H/Ohm
IIC
IIB
IIA
7.63
113
999
0.05
0.14
0.37
22
88
177
or
Gr
oup
Capacitance
in
μ
F
Inductance
in mH
L/R ratio
in
μ
H/Ohm
IIC
IIB
IIA
40
999
999
0.37
1.37
3.25
79
316
632
or
Note 2c
The capacitance and either the inductance or the inductance to r
esistance (L/R) ratio of
the cable
connected between terminals 3 & 4 of
M
TL 7755ac zener diode safety barrier and ter
minals
2 & 3 of a kathar
ometer T
ype 0065XX, must not exceed the following values:
Note 3
The cable may be separate cables or may be installed as separate cir
c
uits within a type ‘A
’ or a type ‘B’
multicor
e
cable as defined in EN60079 - 14: 2014, 12.2.28 (latest edition) subject to the following:
a.
Each cir
c
uit shall be individually scr
e
ened within a type ‘A
’ multicor
e cable.
b.
The peak voltage of any other cir
cuit within a type ‘B
’ multicor
e cable must not exceed 60 volts.
Note 4
The installation must comply with national r
equir
ements
Note 5
The system must be marked with a durable label. The label should appear on or adjacent to the principal
item of electrical apparatus in the system or at the interface be
intrinsically safe cir
cuits.
This marking shall include the wor
d SYST or SYSTE
M
, e.g.
‘BAS SYSTE
M
No Ex 01E2044’ or ‘BAS No Ex 01E2044 SYST’
Note 6
A
junction box, if used, must satisfy the r
equir
e
ments of Clauses 6.1 and 6.3.1 of EN60079:11 (latest edition).
Safe Ar
ea
If Required
Safe Area Apparatus
See Note 1
Zener Diode
Safety Barrier:
M
TL 7755ac
CERT No BAS 01 ATEX 7217
IEC Ex BAS 04.0025
Hazar
dou
s
Ar
ea
2
3
1
4
TB5
18
17
POWER SUPPL
Y
TYPE 4234 500/501
CERTIFIED [Ex ia Ga] IIC
(–20
°
C
≤
Ta
≤
+55
°
C)
CERTIFICA
TE No
BAS 01 A
TEX 7041
-
+
2
1
3
RS1
–
+
4 –
1+
9
10
3 –
2+
KA
THARO
M
ETER
TYPE 0065XXX
CERTIFIED Ex ia IIC T4 Ga
CERTIFICA
TE No
BAS 01 A
TEX 1042
(–20ºC ≤ Ta ≤ +55ºC)
See Note 1
Junction boxes (if r
equir
ed) see note 6.
Location: Hazar
dous or Safe Ar
ea
RV
1
See Notes 2 & 3 for cable details
Display/Control Unit
M
odel 6553
CERTIFIED [Ex ia Ga] IIC
(–20ºC ≤ Ta ≤ +40ºC)
CERT No BAS 01 ATEX 7043
& IECEx BAS 04.0025
2a
2b
2c
I.S. Earth
Gr
oup
Capacitance
in
μ
F
Inductance
in mH
L/R ratio
in
μ
H/Ohm
IIC
IIB
IIA
38
999
999
0.40
1.20
3.20
75
225
600
or
Note 2b
The capacitance and either the inductance or the inductance to r
esistance (L/R) ratio of
the cables
connected between (a) terminals 17 & 18 of the gas monitor type 6553 and terminals 9 & 10
of a kathar
ometer T
y
pe 0065XX.
(e.g. within the UK the standard EN60079-14: (latest edition) is used).