background image

Example: How many air filtration devices (each with 600 CFM rated airflow) would be required to 

provide 8 ACH (including a safety factor) in a 40ft L x 24ft W x 10ft H containment area? 

a.

 

V = 40ft x 24ft x 10ft = 9600ft³ 

b.

 

 Design ACH = 8 

c.

 

Quantity of AFD required = (9600ft³ x 8 ACH) / (600CFM x 60) = 76,800/36,000 = 2.13 

units 

d.

 

2.13 units → 3 units required. 

 

 

ELECTRICAL REQUIREMENTS 

1.

 

The PREDATOR® Portable Air Scrubber requires a minimum of 110 volts AC, 60 Hz to operate properly; 

however, maximum airflow performance requires 120 volts AC, 60 Hz. 

2.

 

Due to momentary start-up current surge, the unit requires a 15 amp circuit that is free of other loads. 

3.

 

Extension cords used for this unit must be UL-listed, heavy duty No. 14/3 AWG SJTW industrial grade 3-

wire type. Use of larger numerical gauge (lower capacity wire) power cord(s) may result in electrical 

shock, fire hazards and/or damage to unit. The cord(s) must be in good condition and in continuous 

lengths (no splicing) and should not exceed a total of 50 feet in length. Make certain that any extension 

cords used do not reduce power to the unit to less than 110 volts. Use of a voltmeter to confirm 

adequate voltage is recommended. 

4.

 

Check to ensure that any circuit to which the unit is connected is protected by a 15 ampere circuit 

breaker. The unit itself is equipped with a 12 amp circuit breaker. 

5.

 

This unit should be connected to a three-prong, properly grounded electrical outlet equipped with a 

Ground Fault Circuit Interrupt (GFCI) device.  A GFCI is an electrical safety device that will trip the circuit 

and stop the flow of electricity if leakage of current is detected. 

Important Note: The GFCI on this unit's control panel only detects leakage of current from the unit or 

an electrical device plugged into the GFCI.  This unit should be plugged into a GFCI receptacle at the 

power source to protect the power cord and the unit.  This GFCI will trip the circuit if it detects 

leakage of current from the power cord or unit. 

6.

 

To avoid personal injury, fire hazards and/or damage to the unit's electrical system and power cord, do 

not connect or disconnect the power cord to an electrical outlet unless the speed control switch is 

“OFF”. 

 

 

 

 

 

Summary of Contents for PREDATOR PRED750

Page 1: ...ODEL PRED750 INSTRUCTION MANUAL Ⓓ ABATEMENT TECHNOLOGIES INC U S PATENT D742495 CANADIAN PATENT 2852880 Abatement Technologies Inc Abatement Technologies Inc Georgia USA 800 634 9091 Abatement Technologies Ltd Ontario Canada 905 871 4720 www abatement com ...

Page 2: ... N H502 Alternate Second Stage Filter 2 High Capacity Vapor Lock Carbon Filter P N VL1002 3 Final Stage 99 97 HEPA Filter P N H161606 99 4 HEPA Filter Retaining Brackets 5 Motorized Impeller located inside cabinet 6 Pre filter Access Door 7 Control Panel 8 Carrying Handle 9 Air Intake 10 nominal diameter 10 Exhaust Outlet 10 nominal diameter ...

Page 3: ...re filter for capturing low concentrations of odors vapors gases and volatile organic compounds collectively known as OVG is also available Types of contaminants captured by particulate pre filters HEPAfilter or carbon filters Dirt Lung damaging particles Low concentrations of OVG Dust Metal fumes Low concentrations of Volatile Organic Compounds VOC Drywall dust Smoke Saw dust Mold and fungal spor...

Page 4: ... by exposing OVG particles to multiple passes through the Vapor Lock filter It is almost impossible to provide accurate estimates to two commonly asked questions how much time will it take to capture all of the OVG and how do I know when a carbon filter should be replaced Unfortunately unknown factors such as concentration levels fresh air intake volume temperature and humidity prevent establishme...

Page 5: ...50 feet in length Make certain that any extension cords used do not reduce power to the unit to less than 110 volts Use of a voltmeter to confirm adequate voltage is recommended 4 Check to ensure that any circuit to which the unit is connected is protected by a 15 ampere circuit breaker The unit itself is equipped with a 12 amp circuit breaker 5 This unit should be connected to a three prong prope...

Page 6: ...isconnecting it from an electrical outlet Failure to do so will cause arcing and could result in personal injury fire hazards and or damage to the unit Do not disconnect the power cord from supply receptacle while the unit is operating Warning To reduce risk of electrical shock do not expose this unit to water or rain Do not touch the electrical outlet or power cord s with wet hands or while stand...

Page 7: ...ctrical outlet 2 Power Indicator Green light that indicates speed control switch is ON and system is connected to power source 3 Speed Control Switch Serves as the power switch and provides a variable adjustment to the speed of the motorized impeller 4 Filter Change Indicator Red light that indicates excessive restriction on intake or loading of the filter s and that filter change procedures shoul...

Page 8: ...utside of the containment area either directly to the outdoors or into another part of the building To maintain negative pressure the air exhaust must exceed the air supply by the greater of 10 or 170 m3 h 100 CFM To achieve this differential the air supply volume to the area may have to be reduced Negative pressure levels should be continuously monitored 2 Recirculation used to reduce concentrati...

Page 9: ...ing Guide STACKING THE UNITS The PRED750 Portable Air Scrubber units can be stacked up to 3 units high total The bottom of the unit is designed to nest into the top of another PRED750 unit Since the filters are accessed through a hinged door the filters can be changed while in the stacked configuration It is not recommended to stack more than 3 units high due to safety as well as the compounding w...

Page 10: ... manual Filters can be changed earlier if desired to maintain a minimum required flow rate The unit should be cleaned with a damp cloth or a water based cleaner sanitizer as needed Do not use harsh chemicals solvents or detergents to clean the unit Warning Keep electrical components dry as their exposure to liquids poses a safety hazard and can damage components Test the GFCI located on the unit s...

Page 11: ...ontaminant indicating that the filter should be replaced Note The filters are not reusable therefore do not attempt to clean and reuse them Caution Abatement Technologies PREDATOR Portable Air Scrubber units are designed to meet or exceed standards for high efficiency air filtration equipment Use only Abatement Technologies parts including replacement filters Use of non Abatement Technologies part...

Page 12: ... control panel the gasketed side of the HEPA filter will be against the internal wall Note The HEPA filter is delicate and should be handled with care When removing or reattaching the HEPA filter retaining brackets do not touch the filter media otherwise damage to the filter and leakage of contaminated air could result 6 Replace the two metal brackets and secure the brackets with the screws Import...

Page 13: ...llows daisy chaining Up to 5 PRED750 units can be daisy chained together including the unit that is plugged into the building receptacle Pre filter access Hinged no tools pre filter access door with turn and latch closure and neoprene gasket First stage pre filter 1 deep coarse particulate pre filter Part Number F621 Second stage pre filter 2 deep pleated particulate pre filter Part Number H502 Al...

Page 14: ...gth of flex duct or eliminate restrictions Remove carbon filter from polybag Note If the unit does not start or malfunctions after carefully following the TROUBLESHOOTING GUIDE call Abatement Technologies service department at 800 634 9091 U S or 905 871 4720 Canada for assistance COMPONENT REPLACEMENT Warning To reduce the risk of fire electrical shock or personal injury always turn the unit OFF ...

Page 15: ...pecifications shall be held for Purchaser s shipping instructions which instructionsPurchasershall furnishpromptlyuponrequest ATI sliabilityshallinnoeventextend beyond replacement repair or refund of the purchase price and ATI shall not be liable under any circumstances for special contingent or consequential damages nor for loss damages or expenses directly or indirectly arising from the use of t...

Page 16: ...15 ...

Page 17: ...16 ...

Page 18: ...17 ...

Page 19: ...TCH13 CAM LATCH 2 13 HARDWRE153 HINGE 2 14 HARDWRE137 SHORT RUBBER FOOT 2 15 HARDWRE138 LONG RUBBER FOOT 2 16 1753 CONTROL PANEL BOX 1 17 ELE164 CAPACITOR 1 18 CTRLPNL101 CONTROL PANEL ASSEMBLY 1 19 1754 CONTROL PANEL PLATE 1 20 H5015 SPEED CONTROLLER 1 21 H5016 SPEED CONTROL KNOB 1 22 LAMP08 AMBER LAMP 1 23 LAMP10 GREEN LAMP 1 24 ELE71 GFCI RECEPTACLE 1 25 ELE152 12 AMP CIRCUIT BREAKER 1 26 ELE22...

Reviews: