Error Messages
Message Icon
Description
Er01
“PUMP
ON”
flashing
Problem with pump or the drain tube is
kinked.
Er02
N/A
Check coil temperature sensor at the
side of coil and the sensor cable.
Er03
N/A
Check ambient temperature sensor in
the front of the coil and the sensor cable.
Note:.
When Er01 or Er02 error message displays, the dehumidification
cycle will stop automatically. The machine will revert to
STANDBY MODE but will still be on unless manually turned off.
Contact Abatement Technologies for service.
When Er03 error message displays, the dehumidification cycle is
still on. Contact Abatement Technologies for service.
Indication Light:
Status
Colors
Description
Off
N/A
Machine is off.
On
Red
Machine is on.
On
Green
Machine dehumidification cycle is on.
Maintenance
WARNING!
Always unplug any dehumidifier before performing
maintenance procedures.
Before Each Use
•
Inspect the electrical cord for damage.
•
Inspect condensate pump drain tube.
Make sure the drain
tube is completely unwrapped and not kinked. Failure to
do so can cause water to back up in the pump and leak
out. The control panel may signal this problem by
displaying “ER01
•
Inspect filter.
Look for accumulated dust and dirt that
would restrict airflow through the filter into the unit. If any
is visible, vacuum out the debris.
Do not wash the filter
,
as it will reduce the effectiveness of the electrostatic
material.
Important:
Replace the filter after:
•
It has been vacuumed clean 3 times.
•
It has been used on a mold remediation job.