PanelView Plus/VersaView CE Terminals and Display Modules
7
Publication 2711P-IN001B-MU-P
Enclosures
The terminals must be mounted in a panel or enclosure to protect the internal
circuitry. The terminals meet NEMA Type 12/13 and 4X ratings only when mounted
in a panel or enclosure with the equivalent rating.
When the terminal is not mounted in a panel, it is not secure or safe for operation.
You must comply with the NEMA Type 4 requirements for environmental
specifications.
Clearances
Allow adequate clearances around the terminal, inside the enclosure, for adequate
ventilation. Consider heat produced by other devices in the enclosure. The ambient
temperature around the terminals must be between 0…55 °C (32…131 °F).
Minimum clearances for ventilation are:
•
top and bottom clearance: 51 mm (2 in)
•
side clearances: 25 mm (1 in)
Maximum side clearance for insertion of memory card is 102 mm (4 in).
Required Tools
Besides the tools required for the panel or enclosure cutouts, you will need the
following for installation:
•
small slotted screw driver
•
torque wrench (in-lb)