3.
Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.68 Nm (6 in-lbs).
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
I/O Memory Mapping
Input Data File
For each input module, slot x, word 0 in the input data file contains the current
state of the field input points.
r= read
TIP
If you need to remove the finger-safe cover, insert a
screw driver into one of the square, wiring holes and
gently pry the cover off. If you wire the terminal block
with the finger-safe cover removed, you will not be able
to put it back on the terminal block because the wires
will be in the way.
Wire Type
Wire Size
Terminal Screw
Torque
Retaining Screw
Torque
Solid
Cu-90°C (194°F)
#14 to #22 AWG
0.68 Nm (6 in-lbs)
0.46 Nm (4.1 in-lbs)
Stranded
Cu-90°C (194°F)
#16 to #22 AWG
0.68 Nm (6 in-lbs)
0.46 Nm (4.1 in-lbs)
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r