RSMD-CM Technical Guide
LCD SCREENS
Alarms History Screens and Protected Screens Map
ALARM
HISTORY
Protected Screens Map
Refer to the following map when navigating through the LCD
Protected Screens. From the RSMD-CM Screen, press
<ENTER>
twice to get to the Software Screen. Then hold the
<UP>
button
for five seconds. To scroll through the rest of the screens, press
the
<MENU>
button.
RSMD
1067vxxx
E-BUS
+0
SOFTWARE
1067vxxx
Hold
for five seconds.
CONFIG
DIAGNSTC
ALARM
COUNTS
ADDRESS
1(152)
ENTER TO
EXIT
Alarm History Screens
The ALARM HISTORY Screen displays past alarms, if any, and
how long ago the last of each type occurred. From the ALARM
HISTORY Screen, press
<ENTER>
to scroll through the history
screens.
The Alarm will appear on the first line and the second line will
display when each alarm last occurred. As a result, the alarms
listed on the ALARMS screen will be abbreviated as follows in
order of the way they are listed in the prior ALARMS screen
section.
NOTE:
The screen will display minutes for the first 60
minutes of alarm occurrence, hours for the next
72 hours of alarm occurrence, and days for the
next 30 days of alarm occurrence. After 30 days,
the alarms will clear. Alarm history is not stored
in memory. So, if power is lost, the alarms will
clear.