59
Condenser Fan Electronically
Commutated Motor (ECM) Startup
The fan cycling option uses a fan cycle switch
to switch between one of the discrete speed
inputs (see
Table 19) on the motor thus cycling between
two preset speeds based upon discharge
pressure of the unit. By connecting 24VAC
to a single or combination of the yellow,
white, or orange wires, the motor will run at
the discrete speeds in
Table 19.
With Customer Provided Unit Controls or
AAON Condenser Head Pressure Module is
used for variable speed control of the motor
to maintain a head pressure. The motor is
factory wired to the PWM outputs of the
AAON Condenser Head Pressure Module.
See AAON literature for further information.
(https://www.aaon.com/Controls)
Note
High voltage wires out of the motor:
Black & Brown - 1 Phase Line Voltage
Green - Ground
Low control voltage wires out of the motor:
Blue - Common
Yellow - Variable Speed Control
Table 19 - ECM Condenser Fan Cycling Options
Color
Terminal
Customer
Connection
Option 1
Option 2
Option 3
Option 4
Option 5
Black
0.50 BWS
L1
208-230
VAC
208-230
VAC
208-230
VAC
208-230
VAC
208-230
VAC
Brown
0.50 BWS
L2
208-230
VAC
208-230
VAC
208-230
VAC
208-230
VAC
208-230
VAC
Green
#10 EYELET
Ground
GND
GND
GND
GND
GND
Blue
0.50 BWS
Common
Common
24 VAC
24 VAC
24 VAC
24 VAC
Yellow
0.50 BWS
Signal
PWM
24 VAC
24 VAC
White
0.50 BWS
Signal
24 VAC
24 VAC
Orange
0.50 BWS
Signal
24 VAC
24 VAC
RPM 300-1100
300
500
850
1100
Rotation
CCW
CCW
CCW
CCW
CCW
ECM Toolbox ID
Variable
Speed 4
Speed 3
Speed 2
Speed 1
20% PWM RPM
300
100% PWM RPM
1100
VFD Controlled Condenser Fan Startup
With Customer Provided Unit Controls the
VFD’s are factory provided and factory
programmed. VFD’s receives input from
pressure transducers on each refrigerant
circuit and vary the fan speed based on the
pressure inputs to maintain a discharge
(head) pressure. Standard pressure setpoint is
340 psi for standard air-cooled systems and
400 psi for modulating hot gas reheat air-
cooled systems.
With the AAON Condenser Head Pressure
Module is used to maintain a discharge
pressure. The VFD is factory wired to the
outputs of the AAON Condenser Head
Pressure Module. See AAON literature for
additional information.
(https://www.aaon.com/Controls).
Summary of Contents for RN Series
Page 2: ......
Page 32: ...32 Figure 5 RN Series 6 8 and 10 ton Unit Isolator Locations ...
Page 33: ...33 Figure 6 RN Series 9 and 11 15 ton Unit Isolator Locations ...
Page 34: ...34 Figure 7 RN Series 16 25 and 30 ton Unit Isolator Locations ...
Page 35: ...35 Figure 8 RN Series 26 31 50 60 and 70 ton Unit Isolator Locations ...
Page 36: ...36 Figure 9 Steel Mounting ...
Page 102: ...102 Figure 56 Example 6 50 60 70 ton through the Base Gas Piping ...
Page 105: ...105 Gas Heater Operating Instructions Figure 58 Gas Heater Instructions ...
Page 129: ...Maintenance Log E Coated Coil ...