LCD DISPLAY SCREENS
MODGAS-XWR-1 Technical Guide
26
Setpoint & Force Valve Screens
Force Valve Screens
Refer to the following map when navigating through the Force Valve
Screens. From the FORCE VALVE Screen, press
<ENTER>
.
At the
V1 and V2 FORCE ON/OFF screens, press the
<UP>
arrow key to
turn the FORCE MODE on and press the
<DOWN>
arrow key to turn
the FORCE MODE off . Use the
<UP>
and
<DOWN>
arrow keys to
increase and decrease the percentage.
FORCE
VALVES
STAGE 1 FORCE
ON/OFF
V1 POSITION
X%
FORCE VALVE 1 PERCENTAGE
This screen only appears when Stage 1 Force is on.
Press the
<UP>
button to turn the Force Mode on. Press the
<DOWN>
button to turn the Force Mode off .
Press the
<UP>
button to increase the percentage. Press the
<DOWN>
button to decrease the percentage.
NOTE:
When you turn the Force Mode back off or after 10 minutes of no
keypad input, the valve will go to zero and the relays will turn off .
STAGE 2 FORCE
ON/OFF/DISABLED
V2 POSITION
X%
FORCE VALVE 2 PERCENTAGE
This screen only appears when Valve 2 Force is on.
Press the
<UP>
button to turn the Force Mode on. Press the
<DOWN>
button to turn the Force Mode off . If the screen says disabled, on/off
selection is not possible.
Press the
<UP>
button to increase the percentage. Press the
<DOWN>
button to decrease the percentage.
STAGE 3
FORCE ON/OFF
STAGES 3 & 4 FORCE ON / OFF
The Stages Force Screens will allow you to force each stage on or off .
Press the
<UP>
button to turn the Force Mode on. Press the
<DOWN>
button to turn the Force Mode off .
STAGE 4
FORCE ON/OFF
RESET SP
40-200°F
5-93°C
RESET HEATING SUPPLY AIR SETPOINT
This is maximum temperature at which the Supply Air Temperature will
reset to. The Setpoint Screen will display only in stand-alone mode.
Minimum
Default
Maximum
40°F
5°C
120°F
49°C
200°F
93°C