MODGAS-XWR2-B Technical Guide
COMMUNICATIONS WIRING
Two Modulating Valves, Two Ignitors, One Stage (2V2IGN1S)
This configuration is used to control two modulating gas valves (one
on each terminal connector), in which the first and second valves
operate together for one modulating stage. One valve is connected
to Heat 1 (RLY3) and the second valve is connected to Heat 2 Relay.
Use an E-BUS cable connecting to an E-BUS port on the controller..
Modulating
Gas Valve 1
(Modulates with
Valve 2 as 1 Stage
Proof of Ignition
Signal 1 (24 VAC)
Heat Valve 1 (Stage 1)
Check your Fan Relay Wiring (RLY1)
Schematic for proper wiring.
Heat Valve 2 (Stage 1)
Fixed Heat Stage 3
Fixed Heat Stage 4
ASSEMBLED IN USA
U15
D13
R
R
R
R
L1
R61
C28
SERIAL #
POWER
COMM
ALARM
STATUS
TB3
GND
AUX AIN
J3
GND
1
2
SAT
OPTIONS
RESET IN
D8
HEAT EN
D7
AUX BIN
GND
J1 U1
TB2
R1
YS102408 REV 3
TB1
RLY1
RLY2
RLY3
RLY4
RLY5
RLY6
COMMON
PO-IGN1
P3
D9
R33
R1
P1
PO-IGN2
P4
D10
R36
R2
Q2
R5
P2
C35
.01UF
R8
R22
R18
R16
R12
R13
R42
R44
D14
SOFTWARE
C22
C27
GAS VALVE 2
GAS VALVE 1
ALARM
UP
DOWN
ENTER
MENU
AAON P/N: ASM06909
MODGAS-XWR2-B
LABEL P/N:
G112180
DUAL
E-BUS
+24 V
AC
GND
CONTACT
RATING IS
1 AMP MAX
@ 24 VAC
COMMON
RELAY
OUTPUTS
GAS VALVE
TERMINALS
GAS
VAL
VE 1
GAS
VAL
VE 2
INPUT TERMINALS (TYPE)
HEAT ENABLE (BI)
AUX. (BI)
GND
RESET IN (AI)
SAT IN (AI)
GND (AI)
GND
AUX. (AI)
www.aaon.com
LOW SPEED
HEAT 1
HEAT 2
HEAT 3
HEAT 4
PROOF OF IGNITION 1
PROOF OF IGNITION 2
FAN
NOTES:
1. 24 VAC must be connected so that all ground wires
remain common.
2. All wiring to be in accordance with local and national
electrical codes and specifications.
GV1
CR2
H1
Line
40 VA
transformer
minimum
GND
18-30
VAC
H2
Proof of Ignition
Signal 2 (24 VAC)
GV2
Modulating
Gas Valve 2
(Modulates with
Valve 1 as 1 Stage
Supply Air
Temperature
Sensor
Mount in unit
supply air duct
Connect Supply Air Temperature Sensor
to AI2 (VCB-X) or AI3 (VCCX2) and GND
on main controller
E-BUS cable connects to the
VCCX2 or VCB-X Controller's
E-BUS port
See SAT OPTIONS Tables in
Appendix A
for
Jumper Settings.
Only one Supply Air Temperature Sensor can be
used per application.
Combustion
Fan Enable
Combustion Fan
Low Speed
CR1
Figure 10: Communications Wiring - One Modulating Valve, Two Ignitors, One Stage
NOTE:
Up to two additional fixed heat stages can be
configured by using Heat 3 (RLY5) and Heat 4
(RLY6). If additional fixed stages are required, these
should be configured and wired to the AAON unit
controller’s relays.