22
MODGAS-X Technical Guide
LCD SCREENS
MODGAS-X Screens
MODGAS-X
1044 V.XXX
S/A MODE
In Stand-Alone Mode, the screen will display S/A MODE or S/A
MODE LOCKED. In Communications Mode, the screen will display
COMM MODE and the items below will scroll through the screen:
1. Number of good packets being received. Example: +XXXX.
2. Number of checksum errors. Example: C-XXXX
3. Number of packet length errors. This will stop at 9999 until
power is cycled. Example: P-XXXX.
4. Number of initialization errors if communication is I
2
C.
Example: I-XXXX.
SOFTWARE
1044 V.XXX
CURRENT SOFTWARE VERSION
ADDRESS
1 (138)
CURRENT BOARD ADDRESS
Number in parenthesis is E-BUS address.
VALV CONFG
0-20 VLT
VALVE CONFIGURATION
0-20 Volt (standard MODGAS-X Module)
0-10 Volt (10-to-1 ratio)
MODGAS-X Screens
From the MODGAS-X Screen, press
<ENTER>
to scroll through
the screens.
# STAGES
T=2 M=2
NUMBER OF STAGES CONFIGURED
T = Total stages fixed and modulating. M = Total modulating stages.
EBUSTEST
XX
EBUS TEST