AAON MHGRV-X Field Technical Manual Download Page 11

11

MHGRV-X Field Technical Guide

OPERATION MODES

Additional Features

5.  Relay Operation

•  Fan Relay will be activated in this mode.
•  Compressor Relay will be activated in this mode.
•  Valve Relay will be activated in this mode after 

the initial 30 seconds.

•  Auxiliary Relay 

 

It will be activated if the Reheat Valve stays 

at 100% for two minutes and the Supply Air 

Temperature is 5°F below the Supply Air 

Setpoint.

 

It will deactivate if the Reheat Valve stays at 0% 

for two minutes and the Supply Air Temperature 

is 5°F above the Supply Air Setpoint.

Communications Operation

In this mode, the MHGRV-X behaves as an expansion board for an 

AAON unit controller. The controller begins the dehumidification 

process when the AAON unit controller makes a request to the 

MHGRV-X for dehumidification. At that time, the controller 

will activate the “FAN” output to energize the HVAC unit fan. 

At the same time, the controller will initiate Cooling Mode by 

energizing the “CMP” output starting the HVAC unit compressor. 
In addition, the MHGRV-X will open the Hot Gas Reheat Coil by 

activating the “VALVE” output which opens the Reheat Solenoid 

Valve. At this time, the MHGRV-X will start to modulate the 

Modulating Hot Gas Reheat Valve. The controller will modulate 

the MHGR valve to maintain the Supply Air Temperature 

Setpoint by activating the stepper motor outputs on the MHGR 

valve. The Supply Air Setpoint is set by programming the HVAC 

unit controller. If Supply Air Temperature Reset is used, it will 

initiate when the HVAC unit controller ends a request to reset 

the Supply Air Temperature. 
The Supply Air Temperature will be reset towards the Supply Air 

Reset Temperature Setpoint stored in the HVAC unit controller. It 

will send a request to move towards the Supply Air Temperature 

Reset Setpoint based on its setpoints and configuration. 

The controller will conclude the Dehumidification process 

when the HVAC unit controller sends a request to terminate 

Dehumidification or a Cooling or Heating Override request is 

made by the HVAC unit controller. Any setpoints or signals at 

the inputs to the MHGRV-X will be ignored. 

Auxiliary Mode Communicating

1.  Same as the Stand-Alone Auxiliary Mode, but the 

Reheat Enable and Auxiliary Valve position will be 

sent using E-BUS commands.

Additional Features

Reheat Coil Flush

To assure positive oil return to the compressor, the Hot Gas 

Reheat Coil will be flushed of liquid refrigerant by moving the 

Modulating Gas Reheat Valve to its maximum position for a 

short interval. 

Cooling Flush

If the unit is in cooling mode, a flush will occur when the unit’s 

flush cooling interval timer has elapsed. The time is accumulated 

whenever it is in cooling mode and resets after each flush cycle. 

The flush cooling interval timer is a setpoint that is configurable 

using the keypad and display (0 to 120 minutes in 10 minute 

increments). 

Reheat Mode Flush

If the unit is in dehumidification mode and the valve is below 

70% for the flush reheat interval timer value, a flush will occur. 

If the valve goes above 70%, the timer is reset. The flush reheat 

interval timer is a setpoint that is configurable using the keypad 

and display (0 to 120 minutes in 10 minute increments). 

Condenser Coil Flush

If Condenser Coil Flush is configured and the unit is in 

Dehumidification Mode and the reheat valve is above 70% for 

the flush reheat interval timer value, a condenser flush will occur. 

This shares the timer with the reheat flush so if the valve is below 

70% a Reheat Flush would occur.

Optional Second Stage Reheat

On larger systems, where more hot gas reheat capacity may be 

required, a two-position Hot Gas Reheat Valve can be connected 

to the MHGRV-X to be used in conjunction with the Modulating 

Hot Gas Reheat Valve. Any time the reheat demand moves above 

the Modulating Hot Gas Reheat Valve capacity, this  two-position 

valve would be energized to supply additional hot gas to the 

Hot Gas Reheat Coil. As the reheat demand is satisfied, the 

MHGRV-X will de-energize the  two-position valve and control 

reheat with the Modulating Hot Gas Reheat Valve. 

Summary of Contents for MHGRV-X

Page 1: ...MHGRV X Controller Field Technical Guide...

Page 2: ...21 AAON Inc All rights reserved throughout the world AAON is a registered trademark of AAON Inc Tulsa OK AAON assumes no responsibility for errors or omissions in this document This document is subjec...

Page 3: ...s Map and Main MHG REHEAT Screens 13 Status and Alarm Screens 14 Setpoint and Force Valves Screens 15 TROUBLESHOOTING 16 LED Diagnostics 16 Alarms 17 Other Checks 18 APPENDIX A SAT SENSOR 20 Supply Ai...

Page 4: ...21 Table 9 Stand Alone Mode SAT OPTIONS Jumper Settings 21 Table 10 Communications Mode SAT OPTIONS Jumper Settings 21 Table 11 Reheat Expansion Module ALARM LED Blink Codes 27 FIGURES Figure 1 MHGRV...

Page 5: ...sing the MHGRV X to replace an existing MHGRV II Controller see Appendix B page 22 for details See Figure 1 this page for dimensions Features The MHGRV X provides the following Can be operated as a st...

Page 6: ...ire size for all sensors should be 24 gauge Some sensors require two conductor wire and some require 3 or 4 conductor wire 5 Minimum wire size for 24 VAC thermostat wiring should be 22 gauge 6 Be sure...

Page 7: ...rature Sensor is attached to the AAON unit controller See Figure 2 this page See the SATWiring Conditions Table and SAT OPTIONS jumper settings in Tables 8 and 10 page 21 Figure 2 MHGRV X to AAON Unit...

Page 8: ...Transformer Minimum Mount In Supply Air Duct RED GRN WHT BLK Condenser Valve 1 HGR Valve 1 RED GRN WHT BLK COMM See SAT OPTIONS table for Jumper Settings Only one Supply Air Temperature Sensor can be...

Page 9: ...g Override Used only in Stand Alone operation When a call for heating is initiated by the HVAC unit this interlocked 24 VAC wet contact closure is used to override the MHGRV X Dehumidification Mode CO...

Page 10: ...can be used in two different modes of operation These modes behave in a similar manner the main difference is the way they receive information to control the dehumidification process The following is...

Page 11: ...terminate Dehumidification or a Cooling or Heating Override request is made by the HVAC unit controller Any setpoints or signals at the inputs to the MHGRV X will be ignored Auxiliary Mode Communicat...

Page 12: ...tions Figure 4 LCD Display and Navigation Keys Table 3 Navigation Key Functions NAVIGATION KEY KEY FUNCTION MENU Use the MENU key to move through screens within Main Menu categories and return to the...

Page 13: ...ress to go to FORCE VALVE Screens FORCE VALVES Press to scroll through FORCE VALVES Screens Main MHG REHEAT Screens Refer to the following map when navigating through the Main Screens From the MHG REH...

Page 14: ...Valve between 0 100 FORCE The unit is in the Force Mode VLV POS 100 VALVE POSITION 0 to 100 percent SA TEMP XX X SUPPLY AIR TEMPERATURE 40 F to 150 F or 5 C to 65 C If no sensor is detected screen wil...

Page 15: ...LY AIR SETPOINT This is maximum temperature at which the Supply Air Temperature will reset to Will display only in Stand Alone Mode The Reset SAT Setpoint is set by the LCD Display in Stand Alone Mode...

Page 16: ...Normally Open Contact is closed VALVE This green LED will light up to indicate that the relay for the VALVE output is energized and its Normally Open Contact is closed AUX This green LED will light up...

Page 17: ...pen or failed wiring Refer to chart in back of this guide for readings Verify the SAT OPTIONS jumper settings on the MHGRV X for the Supply Air Temperature Sensor Communications Loss Check COMM LED on...

Page 18: ...the resistance set the meter to Ohms Unplug the sensor connector from the board and measure the resistance across the disconnected wires This resistance should match the corresponding temperature from...

Page 19: ...2 607 76 24 4 10158 2 577 78 25 6 9711 2 520 80 26 7 9302 2 465 82 27 8 8893 2 407 84 28 9 8514 2 352 86 30 8153 2 297 88 31 1 7805 2 242 90 32 2 7472 2 187 95 35 6716 2 055 100 37 8 6047 1 927 105 4...

Page 20: ...nt Stand Alone Mode In Stand Alone Mode the SAT Sensor is connected to the MHGRV X If in Stand Alone Mode the MHGRV X is used in conjunction with a Stand Alone MODGAS X the SAT sensor is shared betwee...

Page 21: ...ble Install Supply Air Sensor in AAON unit controller Connect to AAON unit controller using I2 C cable VCM VAV CAV MUA MUA II MUA IID Install Supply Air Sensor in MODGAS X Connect to AAON unit control...

Page 22: ...tep 1 Disconnect power from the MHGRV II Step 2 The Supply Air Temperature Sensor needs to remain installed on whatever controller it is currently on If it is currently installed on the MHGRV II then...

Page 23: ...multiple sets of valves See Figure 8 this page for dimensions Features The Reheat Expansion Module provides the following Up to seven Reheat Expansion Modules can be used Each Reheat Expansion Module...

Page 24: ...ller or Module is not operating correctly General Wiring Information For the wiring diagram to use when the MHGRV X is connected to anAAON unit controller see Figure 2 page 7 For the Stand Alone wirin...

Page 25: ...connectors Up to seven Reheat Expansion Modules can be used Apply power to the first Reheat Expansion Module in a series The last Reheat Expansion Module in a series connects to the MHGRV X using an E...

Page 26: ...il return to the compressor the Hot Gas Reheat Coil will be flushed of liquid refrigerant by moving the Modulating Gas Reheat Valve to its maximum position for a short interval Cooling Flush If the un...

Page 27: ...every second The COMM LED should blink simultaneously on all modules Binary Input LED COMPRESSOR ENABLE This green LED will light up when the Reheat is enabled LED Troubleshooting POWER LED When the R...

Page 28: ...he STATUS LED will blink six times A The valve position displayed on the MHGRV X Status Screen should match the expansion module s valve position The expansion module must have the enable signal activ...

Page 29: ...press the ENTER key once from the main screen It should display S A MODE LOCKED 3 The MHGRV X must be configured for EXP VLVS ENABLED in the MHGRV X Configuration Screens If this is true the COMM LED...

Page 30: ...rved AAON Factory Technical Support 918 382 6450 techsupport aaon com AAON Controls Support 866 918 1100 Monday through Friday 7 00 AM to 5 00 PM Central Standard Time Controls Support website www aao...

Reviews: