37
Figure 4 - Service Access Clearance
Table 2 - Minimum Clearances
Unit Size
Minimum Required
Service Clearance
X =
M2-005
50”
M2-008
50”
M2-011
62”
M2-014
62”
M2-018
84”
M2-022
84”
M2-026
84”
M2-032
96”
M2-036
96”
Lifting the Assembled Unit
Units may be delivered as separate modules
or completely factory assembled with all
modules connected. In the latter case, if the
unit was received fully assembled on a skid,
the recommended method of lifting is to
insert a 1-1/2” steel pipe through the lifting
lugs along the entire length of the unit, then
pick the unit up using a spreader bar
assembly. Refer to the M2 Series Unit Four
Point Lifting Figure and the M2 Series Unit
Eight Point Lifting Figure.
If cables or chains are used to hoist the unit
they must be the same length. Care should
be taken to prevent damage to the cabinet,
coils and condenser fans.
Before lifting unit, be sure that all shipping
material has been removed from unit.
UNIT HANDLING
To prevent injury or death lifting
equipment capacity shall exceed unit
weight by an adequate safety factor.
Always test-lift unit not more than 24
inches high to verify proper center of
gravity lift point to avoid unit damage,
injury or death.
Incorrect lifting can cause damage to
the unit.
X
Coil
Energy
Recovery
Wheel
Module
Energy
Recovery
Wheel
Coil Module
Fan
CAUTION
CAUTION
Summary of Contents for M2 Series
Page 2: ......
Page 5: ...5 Split System Piping Diagrams 98 M2 Series Startup Form 115 Maintenance Log 121 ...
Page 35: ...35 Table 1 Electric and Gas Heating Capacities ...
Page 38: ...38 Figure 5 M2 Series Unit Four Point Lifting ...
Page 39: ...39 Figure 6 M2 Series Unit Eight Point Lifting ...
Page 58: ...58 Figure 32 Supply Fan Banding ...
Page 95: ...95 Figure 52 Filter Layout Viewed from the Upstream Side of the Cooling Coil ...
Page 98: ...98 Split System Piping Diagrams Figure 53 A C Split System Piping Suction Down ...
Page 99: ...99 Figure 54 A C Split System Piping Suction Up ...
Page 100: ...100 Figure 55 A C with LAC Split System Piping Suction Up ...
Page 101: ...101 Figure 56 A C with Modulating Hot Gas Reheat Split System Piping Suction Down ...
Page 102: ...102 Figure 57 A C with Modulating Hot Gas Reheat Split System Piping Suction Up ...
Page 103: ...103 Figure 58 A C with Hot Gas Bypass Split System Piping Suction Down ...
Page 104: ...104 Figure 59 A C with Hot Gas Bypass Split System Piping Suction Up ...
Page 107: ...107 Figure 62 Heat Pump Split System Piping Suction Down ...
Page 108: ...108 Figure 63 Heat Pump Split System Piping Suction Up ...
Page 109: ...109 Figure 64 Heat Pump with Modulating Hot Gas Reheat Split System Piping Suction Down ...
Page 110: ...110 Figure 65 Heat Pump with Modulating Hot Gas Reheat Split System Piping Suction Up ...
Page 111: ...111 Figure 66 Heat Pump with Hot Gas Bypass Split System Piping Suction Down ...
Page 112: ...112 Figure 67 Heat Pump with Hot Gas Bypass Split System Piping Suction Up ...