34
RSMVQ Technical Guide
APPENDIX A: SYSTEM CONFIGURATION
Unit Tonnage Selection and Compressor Type Specification Table
Unit Tonnage Selection
You must enter the tonnage for the unit you are controlling.
Please refer to
Table 8, this page,
to figure out unit tonnage for
the compressor(s) on your system. This is found on the RSMV
Configuration Screen.
Refer to
Table 8, this page,
for compressor type unit tonnage
and minimum and maximum compressor speeds.
RSMV-Q Tonnage Selection
Compressor Tonnage Rating
0 Tons
Figure 15: RSMVQ Unit Tonnage Selection
COMPRESSOR TYPE SPECIFICATIONS TABLE
Compressor Type(s)
Unit Tonnage
Minimum VFD
Compressor Speed* (RPM)
Maximum VFD
Compressor Speed*
(RPM)
Single Danfoss CDS803 VFD
7
900
5250
Single Danfoss CDS303 VFD
8
1000
5100
Single Copeland EVxxxx Modular VFD
Determined by Compressor Model
Single Copeland EVCxxx Packaged VFD
Determined by Compressor Model
Compressor 1 - Danfoss CDS803 VFD
Compressor 2 - On/Off
9
900
5100
13
900
5610
Compressor 1 - Danfoss CDS803 VFD
Compressor 2 - Two Step
11
900
5100
Compressor 1 - Danfoss CDS303 VFD
Compressor 2 - On/Off
N/A
N/A
N/A
Compressor 1 - Danfoss CDS303 VFD
Compressor 2 - Two Step
15
1000
5800
Compressor 1 - Copeland EVCxxx Packaged VFD
Compressor 2 - On/Off
30
1200
4700
Compressor 1 - Copeland EVCxxx Packaged VFD
Compressor 2 - Two-Step
20
1000
4900
25
1200
5500
NOTE
: *Speed limits given are before compressor envelope limits are set. See page 13 for envelope limit information.
Table 8:
Compressor Type Specification Table
Summary of Contents for ASM02293
Page 1: ...RSMVQ Technical Guide ...