11
MODGAS-XWR2 Technical Guide
STAND-ALONE WIRING
Two Modulating Valves, One Ignitor, One Stage (2V1IGN1S)
Figure 5: Stand-Alone Wiring - Two Modulating Valves, One Ignitor, One Stage
This configuration is used to control two modulating gas valves
(one on each terminal connector), in which the first and second
valves operate together for one modulating stage. Both valves
are connected to Heat 1 (RLY3).
If using an MHGRV-X Module along with the secondary
MODGAS-XWR2 in Stand-Alone Mode, the SAT Sensor always
attaches to the primary MODGAS-XWR2.
Fan Enable
Low Speed Fan
Connect SAT Input
to Reheat Board’s SAT
Input if applicable.
Modulating
Gas Valve 1
Proof of Ignition
Signal 1 (24 VAC)
Heat Valve 1
-
0-10VDC
External
Reset Signal
Check your Fan Relay Wiring (RLY1)
Schematic for proper wiring.
ALARM
UP
DOWN
ENTER
MENU
MODGAS-XWR2
AAON P/N: ASM01695
LABEL P/N:
G041530
E-BUS
DUAL
I2C
CONNECT
+24
VA
C
GND
@ 24 VAC
1 AMP MAX
CONTACT
RATING IS
COMMON
RELAY
OUTPUTS
GAS VALVE
TERMINALS
GAS
VA
LVE
1
GAS
VA
LVE
2
INPUT TERMINALS (TYPE)
HEAT ENABLE (BI)
AUX. (BI)
GND
RESET IN (AI)
SAT IN (AI)
GND (AI)
GND
AUX. (AI)
www.aaon.com
LOW SPEED
HEAT 1
HEAT 2
HEAT 3
HEAT 4
PROOF OF IGNITION 1
PROOF OF IGNITION 2
FAN
See SAT OPTIONS Tables for Jumper Settings.
Only one Supply Air Temperature Sensor can be
used per application.
Notes:
1. 24 VAC must be connected so that all ground wires
remain common.
2. All wiring to be in accordance with local and national
electrical codes and specifications.
E-BUS cable can connect to a
secondary MODGAS-XWR2 or to
a 12 Relay E-BUS expansion port
GV1
CR1
CR2
H1
Line
40 VA
transformer
minimum
Supply Air
Temperature
Sensor
Mount in unit
supply air duct
Heat Enable
Signal (24 VAC)
W1
GND
18-30
VAC
Modulating
Gas Valve 2
GV2
Fixed Heat Stage 2
Fixed Heat Stage 3
Fixed Heat Stage 4
NOTE:
Up to three additional fixed heat stages can be
configured by using Heat 2 (RLY4), Heat 3
(RLY5) and Heat 4 (RLY6). Up to 12 additional
fixed stages can be added by using the 12 Relay
E-BUS Expansion Module. (
Figure 8, page 14
).