MODGAS-X Technical Guide
ModRate2
XXXs
MOD RATE 2
Controls the Mod Rate of the second and subsequent stages of heat.
Range: 1-120 seconds.
St@MinDb
XXº
MIN MODE DEADBAND
Range: 0-30 degrees.
NOTE:
If it is set to 0, Min Mode will not initialize and the sequence
will continue to Heating Mode.
MinPosTP
XXXs
MIN MODE RUN TIME
Range: 0-500 seconds.