ISE40A Pressure Switch Setup
1. Enter Function Selection mode – Press and hold the
S
key (> 2 sec.) until the display
reads
F 0
a. If
LoC
is displayed, hold the
S
key for > 5, press the
Down
key once, then press
S
button once to enter the setting.
2. Reset unit to default settings – Press the
Down
key once to navigate to
F99;
Press the
S
key once, then the
Up
arrow once to toggle to
on
; Hold the
S
key and the
Down
arrow
key for > 5 seconds.
3. From F99 press the
UP
key twice to navigate to
F 1
and press the
S
key 3 times until the
display reads
P_1
. Using the
UP and Down
keys set display to the
setting on the
prints
(Aagard standard setting is
65 psi
). Press the
S
key once to display
H_1
. Using
the
UP and Down
keys set display to
1.0
. Press the
S
key 2 times to return to
F 1.
4.
Setting F 2 (P_2) is not necessary for Aagard’s standard application.
5. Now return to the main display by pressing an holding the
S
key for > 2 seconds. This
should bring you to a screen with a low number on it for the current/live reading.
6. The
Out 1
indicator should not be illuminated at this point if system air hasn’t been
applied yet.
System pressure switch settings –
P_1
= 65.0
By setting these switches up in this manner the pressure switch will provide an output when
system pressure gets to
65.0
PSI and it will loose its signal when it drops below
64.0
PSI.