ZSE40 Vacuum Switch Setup
1. Press and hold the
SET
key until the display shows a unit of measurement such as kPa,
psi, ect.
2. Then using the
UP and Down
keys navigate to the correct unit which is
InHg
for inches
of mercury.
3. Now return to the main display by pressing the
SET
key. This should bring you to a
screen with a low number on it for the current/live reading.
4. Press the
SET
key again and the display should read
P_1
toggling to a number and then
back again.
5. Using the Arrow Keys adjust the number to
P_1 setting on prints
which would be the
ON
trigger point of the vacuum switch.
6. Press the
SET
key again to go to
P_2
and set to
P_2 settings on prints
which would be
the OFF trigger point of the vacuum switch. And press the
SET
key again.
7. Displayed will be
P_3
which we leave set at its default. Press the
SET
key again so the
display reads
P_4
and again leave this set at its default.
8. Now press the
SET
key until you are back to the main page which should have a low
number reading on it such as 0.0 to 0.4.
9. The
Out 1
indicator should not be illuminated at this point and you are ready for
production.
System vacuum switch settings – P_1 = 18; P_2 = 15
Secondary vacuum switch settings – P_1 = 15; P_2 = 12
By setting these switches up in this manner the Vacuum switch will provide an output when we get
to
17.0
InHg and it will not loose its signal unless we drop below
15.0
InHg.