15
14.0 Airflow Ratings
15.0 Troubleshooting Guide
Speed 1
Speed 2
Speed 3
Speed 4
Maximum
HFS800C
(8"x12" rectangular exhaust)
250 CFM
375 CFM
500 CFM
625 CFM
750 CFM
HFS800C
(8" diameter round exhaust)
200 CFM
300 CFM
400 CFM
500 CFM
600 CFM
NOTE: Airflow ratings estimates are based on factory and independent testing @ 120 VAC with an air
straightener and a traverse of readings taken with a computing vane-anemometer. Actual results may vary
for various reasons, including motor, blower and HEPA filter tolerances. Factors such as filter loading,
reduced voltage to the motor, and inlet and outlet ducting will reduce airflow. Use these ratings as a
general guideline only as results can vary with each installation.
Unit won’t start when it is
turned “ON.”
Filter loading indicators flashing.
Problem
Possible Cause
Solution
Electrical wiring connections.
Tripped circuit breaker.
Thermal overload on motorized
impeller(s) has tripped.
Loaded filters.
Optional carbon filter not removed
from polybag.
Check condition of wiring and
cabling. Check all electrical
connections to ensure they are in
accordance with wiring diagrams
and schematics.
Reset building breaker. Reset 5 amp
breaker on unit.
Turn unit “OFF,” wait 20-30 minutes
and restart.
Refer to Filter Change Procedures.
Remove from polybag.
NOTE: If unit does not start or malfunctions after carefully following the Troubleshooting Guide, call AAF at
1-888-223-2003.