TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
14
03/18/21
www.atcontrols.com
IOM08139 REVISION 01
COMMS CONFIG submenu
C O M M S
T Y P E :
x x x x
Communication
Type
Sets type of communication protocol when using one of the communication module options. “Comms” command
type must be selected in the
COMMAND CONFIG
submenu.
Modbus
Modbus RTU
MbusTCP Modbus/TCP
Profibus
Profibus DP
U N I T I D :
x x
Unit ID
Actuator ID address. Selectable from 1 to 246
1
B A U D R A T E
x x x x
Baud Rate
Communication channel data rate.
9600, 19200, 57600, 115200 bps
P A R I T Y :
x x x x
Parity
Communication channel parity setting.
None, Odd, Even
T I M E O U T :
x x . x x S
Timeout
Communication timeout. Determines duration of time which the actuator must receive communication before
entering fault condition.
10.00 sec
SYSTEM CONFIG submenu
M O T O R
T Y P E :
x x
Motor Type
Selects type of motor being operated. AC setting is for split-phase AC type motor. DC is for DC motors. This
setting is independent of the AC/DC power supply switch, but should correspond to the switch position.
AC
C Y C L E C N T
O P E N : x x x
C L O S : x x x
Cycle Count
Displays count for open and close position since power supplied to controller.
C L E A R C Y C L
C O U N T S
> >
Clear Count
Clears cycle count. Press [RIGHT] or [CENTER] to select, then press again to confirm and clear counts.
R E S T O R E
D E F A U L T S
> >
Restore Defaults
Restores all settings to their default value. Press [RIGHT] or [CENTER] to select, then press again to confirm and
reset to default values.
S O F T W A R E
V E R S I O N
x x . x x
Software Version
Displays current software revision number.