13.3
Gas details
Description
Unit
TWI 35-200
TWI 45-200
Gas category 2H (G20)
Diameter of the venturi
restrictor
mm
-
-
Nominal Load (gross)
kW
38.9
50.0
Nominal output
kW
35.9
46.2
Supply pressure
mbar
20
20
CO
2
(full load)
vol%
9.0 ± 0.5
9.0 ± 0.5
O
2
(full load)
vol%
4.8 ± 0.9
4.8 ± 0.9
Gas consumption
(1)
m
3
/h
3.7
4.8
NO
x
emission
mg/kWh GCV
53
53
Mass flow rate flue gases
(minimal load)
kg/h
42
42
Mass flow rate flue gases
(nominal load)
kg/h
63
81
Flue gas temperature
(nominal load)
ºC
65
75
Gas category 3P (G31)
Diameter of the venturi
restrictor
mm
6.00
6.00
Nominal Load (gross)
kW
38.0
48.9
Nominal output
kW
35.9
46.4
Supply pressure
mbar
37
37
CO
2
(full load)
vol%
10.0 ± 0.5
10.0 ± 0.5
O
2
(full load)
vol%
5.7 ± 0.8
5.7 ± 0.8
Gas consumption
kg/h
2.7
3.5
NO
x
emission
mg/kWh GCV
61
61
Mass flow rate flue gases
(minimal load)
kg/h
43
43
Mass flow rate flue gases
(nominal load)
kg/h
64
83
Flue gas temperature
(nominal load)
ºC
65
75
1 - Based on 1013.25 mbar and 15°C.
84
Installation, Maintenance and Service part
Summary of Contents for TWI 35-200
Page 6: ...6...
Page 13: ...User part 0313279_TWISTER II_UKUK_V1 1 18 02 2019 13...
Page 14: ...14...
Page 16: ...16 User part...
Page 18: ...18 User part...
Page 25: ...Installation Maintenance and Service part 0313279_TWISTER II_UKUK_V1 1 18 02 2019 25...
Page 26: ...26 User part...
Page 34: ...34 Installation Maintenance and Service part...
Page 54: ...54 Installation Maintenance and Service part...
Page 56: ...56 Installation Maintenance and Service part...
Page 66: ...66 Installation Maintenance and Service part...
Page 72: ...72 Installation Maintenance and Service part...
Page 80: ...80 Installation Maintenance and Service part...
Page 87: ...13 6 Declaration of conformity 0313279_TWISTER II_UKUK_V1 1 18 02 2019 87...